|
This is a "home rule" state. Home rule shifts much of the responsibility for local government from the state legislature to the local community. A county or city that adopts a home rule charter can, amongst other things, enact local energy codes.
This locality is not currently mandating a statewide energy code.
ASHRAE 90.1 - 1989
401.1.2 Electrical Schematic
401.3 Lighting Power Allowance
401.3. Lighting Power Control Credits
401.3.4 Lighting Controls
402.4.1.2 Fenestration
401 ELECTRICAL POWER AND LIGHTING SYSTEMS
Electrical power and lighting systems, other than those systems or portions thereof required for emergency use only, shall meet these requirements.
401.1 Electrical Distribution Systems
401.1.1 Check Metering Single-tenant buildings with a service over 250 kVA and tenant spaces with a connected load over 100 kVA in multiple-tenant buildings shall
have provisions for check metering of electrical consumption.
The electrical power feeders for which provision for check metering is required shall be subdivided as follows:
(a) Lighting and receptacle outlets.
Exception to (a), (b), and (c): 10% or less of the loads on a feeder may be from another usage category.
Subdivided feeders shall contain provisions for portable or permanent check metering. The minimum acceptable arrangement for compliance shall provide a safe method for
access by qualified persons to the enclosures through which feeder conductors pass and provide sufficient space to attach clamp-on or split core current transformers. These enclosures may be
separate compartments or combined spaces with electrical cabinets serving another function. Dedicated enclosures so furnished shall be identified as to measuring function available.
401.1.2 Electrical Schematic. The person responsible for installing the electrical distribution system shall provide the building owner a singleline diagram of the record drawing for the
electrical distribution system, which includes the location of check-metering access, schematic diagrams of non-HVAC electrical control systems, and electrical equipment manufacturer's operating
and maintenance literature.
LIGHTING SYSTEMS AND EQUIPMENT
401.3 Lighting Power Allowance The lighting system shall meet the provisions of Sections 401.3.1 through 401.3.5. As an alternative to Sections 401.3.1 and 401.3.2, the Lighting Compliance
Calculation Computer Program (LTGSTD21) may be used to determine the lighting power allowance for the building or facility.
401.3.1 Building Exteriors The total connected exterior lighting power for the building, or a facility containing multiple buildings, shall not exceed the total exterior lighting power
allowance, which is the sum of the individual allowances determined by multiplying the specific area or length of each area description times the allowance for that area.
Exception: Lighting for outdoor manufacturing or processing facilities, commercial greenhouses, outdoor athletic facilities, public monuments, designated high-risk
security areas, signs, retail storefronts, exterior enclosed display windows, and lighting specifically required by local ordinances and regulations.
TABLE 401.3.1
Exterior Lighting Power Allowance
| Area Description |
Allowance |
| Exit (with or without canopy) |
25 W/lin ft of door opening |
| Entrance (without canopy) |
30 W/lin ft of door opening |
Entrance (with canopy)
High traffic (retail, hotel, airport, theater, etc.)
Light traffic (hospitals, office, school, etc.) |
10 W/ft² of canopied area
4 W/ft² of canopied area |
| Loading area |
0.40 W/ft² |
| Loading door |
20 W/lin ft of door opening |
| Building exterior surfaces/facades |
0.25 W/ft² of surface area to
be illuminated |
| Storage and non-manufacturing work areas |
0.20 W/ft² |
Other activity areas for casual use, such as picnic
grounds, gardens, parks, and other landscaped
areas |
0.10 w/ft² |
| Private driveways/walkways |
0.10 w/ft² |
| Public driveways/walkways |
0.15 W/ft² |
|
| Private parking lots |
0.12 W/ft² |
| Public parking lots |
0.18 W/ft² |
401.3.1.1 Trade-offs of exterior lighting budgets among exterior areas shall be allowed provided the total connected lighting power of the exterior area does not
exceed the exterior lighting power allowance. Trade-offs between interior lighting power allowances and exterior lighting power allowances shall not be allowed.
401.3.2 Building Interiors The total connected interior lighting power for a building, including adjustments in accordance with Section 401.3.3, shall not exceed the total interior lighting
power allowance determined from any of the following:
(a) Using Table 401.3.2a, multiply the interior lighting power allowance value by the gross lighted area of the most appropriate building or space activity. For multi-use buildings, select the
interior lighting power allowance value for each activity using the column for the gross lighted area for that activity. The interior lighting power allowance is the sum of all the wattages for
each area/activity.
(b) Using Table 401.3.2b, c, or d, multiply the interior lighting power allowance values of each individual area/activity by the area of the space and by the area factor from Figure 401.3.2e,
based on the most appropriate area/activity provided. The interior lighting power allowance is the sum of the wattages for each individual space.
(c) Use the Lighting Compliance Calculation Computer Program (LTGSTD21) of RS-1.
When over 20% of the building's tasks or interior areas are undefined, the most appropriate value for that building from Table 401.3.2a shall be used for the undefined
spaces. Exceptions:
(1) Lighting power that is an essential technical element for the function performed in theatrical, stage, broadcasting, and similar uses.
(2) Specialized medical, dental, and research lighting.
(3) Display lighting for exhibits in galleries, museums, and monuments.
(4) Lighting solely for indoor plant growth (between the hours of 10:00 p.m. and 6:00 a.m.).
(5) Emergency lighting that is automatically off during normal building operation.
(6) High-risk security areas.
(7) Spaces specifically designed for primary use by the physically impaired or aged.
(8) Lighting in dwelling units.
401.3.2.1 Trade-offs of the interior lighting power budgets among interior spaces shall be allowed provided the total connected lighting power within the building
does not exceed the interior lighting power allowance. Trade-offs between interior lighting power allowances and exterior lighting power allowances shall not be allowed.
401.3.2.2 Building/Space Activities Definitions of buildings/space activity as they apply to Table 401.3.2a are as follows:
Food Service, fast food, and cafeteria: This group includes cafeterias, hamburger and sandwich stores, bakeries, ice cream parlors, cookie stores, and all other
kinds of retail food service establishments in which customers are generally served at a counter and their direct selections are paid for and taken to a table or carried out.
Leisure dining and bar: This group includes cafes, diners, bars, lounges, and similar establishments where orders are placed with a wait person.
Offices: This group includes all kinds of offices, including corporate and professional offices, office/laboratories, governmental offices, libraries, and similar
facilities where paperwork occurs.
Retail: A retail store, including departments for the sale of accessories, clothing, dry goods, electronics, and toys, and other types of establishments that
display objects for direct selection and purchase by consumers. Direct selection means literally removing an item from display and carrying it to checkout or pick-up at a customer service
facility.
Mall concourse, multi-store service: This group includes the interior of multifunctional public spaces, such as shopping center malls, airports, resort concourses
and malls, entertainment facilities, and related types of buildings or spaces
Service establishment: A retail-like facility, including watch repair, real estate offices, auto and tire service facilities, parts departments, travel agencies,
and similar facilities, in which the customer obtains services rather than the direct selection of goods.
Garages: This category includes all types of parking garages, except for service or repair areas.
School: This category, subdivided by pre-school/elementary, junior high/high school, and technical/vocational, includes public and private educational
institutions, for children or adults, and may also include community centers, college and university buildings, and business educational centers.
Warehouse and storage: This includes all types of support facilities, such as warehouses, barns, storage buildings, shipping/receiving buildings, boiler or
mechanical buildings, electric power buildings, and similar buildings where the primary visual task is large items.
TABLE 401.3.2a
Interior Lighting Power Allowance, W/ft²
| Building Space Activitya,b |
Gross Lighted Area of Total Building |
0 to
2,000 ft² |
2,001 to
10,000 ft² |
10,001 to
25,000 ft² |
25,001 to
50,000 ft² |
50,001 to
250,000 ft² |
>250,000 ft² |
Food Service:
Fast Food/Cafeteria
Leisure Dining/Bar |
1.50
2.20 |
1.38
1.91 |
1.34
1.71 |
1.32
1.56 |
1.31
1.46 |
1.30
1.40 |
| Offices |
1.90 |
1.81 |
1.72 |
1.65 |
1.57 |
1.50 |
| Retailc |
3.30 |
3.08 |
2.83 |
2.50 |
2.28 |
2.10 |
Mail Concourse
Multi-store Service |
1.60 |
1.58 |
1.52 |
1.46 |
1.43 |
1.40 |
| Service Establishment |
2.70 |
2.37 |
2.08 |
1.92 |
1.80 |
1.70 |
| Garages |
0.30 |
0.28 |
0.24 |
0.22 |
0.21 |
0.20 |
Schools:
Preschool/Elementary
Jr.High/High School
Technical/Vocational |
1.80
1.90
2.40 |
1.80
1.90
2.33 |
1.72
1.88
2.17 |
1.65
1.83
2.01 |
1.57
1.76
1.84 |
1.50
1.70
1.70 |
| Warehouse/Storage |
0.80 |
0.66 |
0.56 |
0.48 |
0.43 |
0.40 |
Notes:
aIf at least 10% of the building area is intended for multiple space activities, such as parking, retail, and storage in an office building, then calculate for each separate building
type/space activity.
bThe values in the categories are building-wide allowances which include the listed activity and directly related facilities such as conference rooms, lobbies, corridors, restrooms,
etc.
cIncludes general, merchandising, and display lighting. |
TABLE 401.3.2b
Unit Interior Lighting Power Allowance
| Common Area/Activitya |
UPD W/ft² |
Auditoriumb
Corridorc
Classroom/Lecture Hall
Electrical/Mechanical EquipmentRoom
Generalc
Control Roomsc |
1.6
0.8
2.0
0.7
1.5 |
Food Service
Fast Food/Cafeteria
Leisure/Diningd
Bar Lounged
Kitchen |
1.3
2.5
2.5
1.4 |
| Recreation/Lounge |
0.7 |
Stair
Active Traffic
Emergency Exit |
0.6
0.4 |
| Toilet and Washroom |
0.8 |
Garage
Auto and Pedestrian Circulation Area
Parking Area |
0.3
0.2 |
| Laboratory |
2.3 |
Library
Audiovisual
Stack area
Card File and Cataloging
Reading Area |
1.1
1.5
1.6
1.9 |
Lobby (General)
Reception and Waiting
Elevator Lobbies
Atrium (Multi-Story)
First 3 Floors
Each Additional Floor |
1.0
0.8
0.7
0.2 |
| Locker Room and Shower |
0.8 |
Office Category 1
Enclosed offices, all open plan offices w/o partitions or w/ partitions* lower than 4.5 ft below the ceiling.e
Reading, Typing, and Filing
Drafting
Accounting |
1.8
2.6
2.1 |
Office Category 2
Open-plan offices 900 ft<² or larger w/ partitions* 3.5 to 4.5 ft below the ceiling. Offices less than 900 ft² shall use category 1c.
Reading, Typing, and Filing
Drafting
Accounting |
1.9
2.9
2.4 |
Office Category 3
Open-plan offices 900 ft² or larger w/ partitions higher than 3.5 ft below the ceiling. Offices less than 900 ft² shall use category 1c.
Reading, Typing, and Filing
Drafting
Accounting |
2.2
3.4
2.7 |
Garage
Common Activity Areas |
1.8 |
Computer/Office Equipment
Filing, Inactive
Mail Room |
2.1
1.0
1.8 |
Shop (Nonindustrial)
Machinery
Electrical/Electronic
Painting
Carpentry
Welding |
2.5
2.5
1.6
2.3
1.2 |
Storage and Warehouse
Inactive Storage
Active Storage, Bulky
Active Storage, Fine
Material Handling |
0.3
0.3
1.0
1.0 |
| Unlisted Space |
0.2 |
*Not less than 90% of all workstations shall be individually enclosed with partitions of at least the height
described.
aUse a weighted average UPD in rooms with multiple simultaneous activities, weighted in proportion to the area served.
bA 1.5 power adjustment factor is applicable for multi-function spaces when a supplementary system having independent controls is installed that has intalled power ≤ 33% of
the adjusted lighting power for that space.
cArea factor of 1.0 shall be used for these spaces.
dUPD includes lighting power required for clean-up purpose.
eArea factor shall not exceed 1.55. |
TABLE 401.3.2c
Unit Interior Lighting Power Allowance
| Common Area/Activitya |
UPD W/ft² |
Airport, Bus and Rail Station
Baggage Area
Concourse/Mail Throughway
Ticket Counter
Waiting and Lounge Area |
1.0
0.9
2.5
1.2 |
Bank
Customer Area
Banking and Lounge Area |
1.1
2.8 |
| Barber and Beauty Parlor |
2.0 |
Church, Synagogue, Chapel
Worship/Congretional
Preaching and Sermon/Choir |
2.5
2.7 |
Dormitory
Bedroom
Bedroom w/ Study
Study Hall |
1.1
1.4
1.8 |
Fire and Police Department
Fire Engine Room
Jail Cell |
0.7
0.8 |
Hospital/Nursing Home
Corridore
Dental Suite/Examination/Treatment
Emergency<</span>
Laboratory
Lounge/Waiting room
Medical Supplies
Nursery
Nurse Station
Occupational Therapy/Physical Therapy
Patient Room
Pharmacy
Radiology
Surgical and OB Suites
General Area
Operating Room
Recovery |
1.3
1.6
2.3
1.9
0.9
2.4
2.0
2.1
1.6
1.4
1.7
2.1
2.1
7.0
2.3 |
Hotel/Conference Center
Banquet Room/Multipurposeb
Bathroom/Power Room
Guest Room
Public Area
Exhibition Hall
Conrference/Meetingb
Lobby
Reception |
2.4
1.2
1.4
1.2
2.6
1.8
1.9
2.4 |
Laundry
Washing
Ironing and Sorting |
0.9
1.3 |
Museum and Gallery
General Exhibition
Inspection/Restoration
Storage (Artifacts)
Inactive
Active |
1.9
3.9
0.6
0.7 |
Post Office
Lobby
Sorting and Mailing |
1.1
2.1 |
| Service Station/Auto Repair |
1.0 |
Theater
Performance Arts
Motion Picture
Lobby |
1.5
1.0
1.5 |
| Retail Establishments—Merchandising and Circulation Area (Applicable to all lighting, including accent and display lighting, installed in merchandising and circulation
areas) |
|
|
Type 1: Jewelry merchandising, where minute examination of displayed merchandise is critical.
|
5.6 |
|
Type 2: Fine merchandising, such as fine apparel and accessories, china, crystal, and silver art galleries and where the detailed display and
examination of merchandise is important.
|
3.2 |
|
Type 3: Mass merchandising, such as general apparel, variety goods, stationary, books, sporting goods, hobby materials, cameras, gifts, and
luggage, displayed in a warehouse type of building, where focused display and detailed examination of merchandise is important.
|
3.3 |
|
Type 4: General merchandising, such as general apparel, variety goods, stationery, books, sporting goods, hobby materials, cameras, gifts, and
luggage, displayed in a department store type of building, where general display and examination of merchandise is adequate.
|
3.1 |
|
Type 5: Food and miscellaneous such as bakeries, hardware and houseware, grocery stores, appliance and furniture stores, where pleasant appearance
is important.
|
2.8 |
|
Type 6: Service establishments, where functional performance is important.
|
2.7 |
Mall Concourse
Retail Support Areas
Tailoring
Dressing/Fitting Rooms |
1.4
2.1
1.4 |
aUse a weighted average UPD in rooms with multiple simultaneous activities, weighted in proportion to the
area served.
bA 1.5 power adjustment factor is applicable for multi-function spaces when a supplementary system having independent controls is installed that has intalled power ≤ 33% of
the adjusted lighting power for that space.
cArea factor of 1.0 shall be used for these spaces.
dUPD includes lighting power required for clean-up purpose.
eArea factor shall not exceed 1.55. |
TABLE 401.3.2d
Unit Interior Lighting Power Allowance
| Indoor Athletic Area/Activityc,f |
UPD W/ft² |
| Seating Area, All Sports |
0.4 |
Badminton
Club
Tournament |
0.4
0.8 |
Basketball/Volleyball
Intramural
College
Professional |
0.8
1.3
1.9 |
Bowling
Approach Area
Lanes |
0.5
1.1 |
Boxing or Wrestling (platform)
Amateur
Professional |
2.4
4.8 |
Gymnasium
General Exercising and Recreation Only |
1.0 |
Handball/Racquetball/Squash
Club
Tournament |
1.3
2.6 |
Hockey, Ice
Amateur
College or Professional |
1.3
2.6 |
Skating Rink
Recreational
Exhibition/Professional |
0.6
2.6 |
Swimming
Recreational
Exhibition
Underwater |
0.9
1.5
1.0 |
Tennis
Recreational (Class III)
Club/College (Class II)
Professional (Class I) |
0.9
1.5
1.0 |
Tennis, Table
Club
Tournament |
1.0
1.6 |
aUse a weighted average UPD in rooms with multiple simultaneous activities, weighted in proportion to the
area served.
bA 1.5 power adjustment factor is applicable for multi-function spaces when a supplementary system having independent controls is installed that has intalled power ≤ 33% of
the adjusted lighting power for that space.
cArea factor of 1.0 shall be used for these spaces.
dUPD includes lighting power required for clean-up purpose.
eArea factor shall not exceed 1.55.
fConsider as 10 ft beyond playing boundaries but less than or equal to the total floor area of the sports space minus spectator seating area. |
Figure 401.3.2e Area Factor Area Factor Formula:

AF = area factor,
CH = ceiling height (ft),
Ar = room area (ft²).
If AF < 1.0 use 1.0; if AF > 1.8 use 1.8.
401.3. Lighting Power Control Credits The interior connected lighting power determined in accordance with Section 401.3.2 can be decreased for luminaires that are automatically controlled
for occupancy, daylight, lumen maintenance, or programmable timing. The adjusted interior connected lighting power shall be determined by subtracting the sum of all lighting power control credits
from the interior connected lighting power. Using Table 401.3., the lighting power control credit equals the power adjustments factors times the connected lighting power of the controlled
lighting.
The lighting power adjustment shall be applied with the following limitations:
(a) It is limited to the specific area controlled by the automatic control device.
(b) Only one lighting power adjustments may be used for each building space or luminaire, and 50% or more of the controlled luminaire shall be within the applicable space.
(c) Controls shall be installed in series with the lights and in series with all manual switching devices.
(d) When sufficient daylight is available, daylight sensing controls shall be capable of reducing electrical power consumption or lighting (continuously or in steps) to 50% or less of maximum
power consumption.
(e) Daylight sensing controls shall control all luminaires to which the adjustment is applied and that direct a minimum of 50% or less of maximum power consumption.
(f) Programmable timing controls shall be able to program different schedules for temporary override with automatic return to the original schedule, and keep time during power outages for at
least four hours.
TABLE 401.3.3
Lighting Power Adjustment Factors
| Automatic Control Devices |
PAF |
| (1) |
Daylight sensing controls (DS), continuous dimming |
0.30 |
| (2) |
DS, multiple step dimming |
0.20 |
| (2) |
DS, multiple step dimming |
0.20 |
| (3) |
DS, multiple step dimming |
0.10 |
| (4) |
DS, ON/OFF |
0.35 |
| (5) |
DS multiple-step dimming and programmable timing |
0.25 |
| (6) |
DS ON/OFF and programmable timing |
0.15 |
| (7) |
DS continuous dimming, programmable timing, and lumen maintenance |
0.40 |
| (8) |
DS multiple-step dimming, programmable timing, and lumen maintenance |
0.30 |
| (9) |
DS ON/OFF, programmable timing, and lumen maintenance |
0.20 |
| (10) |
Lumen Maintenance Control |
0.10 |
| (10) |
Lumen maintenance control |
0.10 |
| (11) |
Lumen maintenance and programmable timing control |
0.15 |
| (12) |
Programmable timing control |
0.15 |
| (13) |
Occupancy sensor (OS) |
0.30 |
| (14) |
OS and DS, continuous dimming |
0.40 |
| (15) |
OS and DS, multiple-step dimming |
0.35 |
| (16) |
OS and DS, ON/OFF |
0.35 |
| (17) |
OS and DS continuous dimming, and lumen maintenance |
0.45 |
| (18) |
OS and DS multi-step dimming, and lumen maintenance |
0.40 |
| (19) |
OS and DS ON/OFF, and lumen maintenance |
0.35 |
| (20) |
OS and lumen maintenance |
0.35 |
| (21) |
OS and programmable timing control |
0.35 |
401.3.4 Lighting Controls
401.3.4.1 Type of Lighting Controls. All lighting systems shall have controls.
Exception: Emergency use or exit lighting.
401.3.4.2 Number of Manual Controls. Spaces enclosed by walls or ceiling-high partitions shall have a minimum of one manual control (on/off switch) for lighting in that space.
Additional manual controls shall be provided for each task location or for each group of task locations within an area of 450 ft(2) or less. For spaces with only one lighting fixture or with
a single ballast, one manual control is required. Exceptions:
(1) Continuous lighting for security.
(2) Systems in which occupancy sensors, local programmable timers, or three-level (including OFF) step control or preset dimming controls are substituted for manual
controls at the ?exchange rate?of one for every two required manual controls, providing at least one control is installed for every 1500 watts of power.
(3) Systems in which four-level (including OFF) step controls or present dimming controls or automatic or continuous dimming controls are substituted for manual controls at
an "exchange rate" of one for every three required manual controls, providing at least one control is installed for every 1500 watts of power.
(4) Spaces that are used as a whole, such as public lobbies, retail stores, warehouses and storerooms.
401.3.4.3 Multiple Location Controls. Manual controls that operate the same load from multiple locations shall be counted as one manual control.
401.3.4.4 Control Accessibility. Lighting controls shall be readily accessible from within the space controlled.
Exception: Controls for spaces that are used as a whole, automatic controls, programmable controls, controls requiring trained operators, and controls for safety
hazards and security.
401.3.4.5 Hotel and Motel Guest Room Control. Hotel and motel guest rooms and suites shall have at least one master switch at the main entry door that controls all permanently wired lighting
fixtures and switched receptacles excluding bathrooms.
Exception: Where switches are provided at the entry to each room of a multiple-room suite.
401.3.4.6 Switching of Exterior Lighting. Exterior lighting not intended for 24-hour use shall be automatically switched by either timer or photocell or a combination of timer and
photocell. When used, timers shall be capable of seven-day and seasonal daylight schedule adjustment and have power backup for at least four hours.
401.3.5 Ballasts
401.3.5.1 Tandem Wiring. One-lamp or three-lamp fluorescent luminaries that are recess mounted within 10 ft center-to-center of each other, or pendant
mounted, or surface mounted within 1 ft of each other, and within the same room, shall be tandem wired, unless three-lamp ballasts are used.
401.3.5.2 Power Factor. All ballasts shall have a power factor of at least 90%. Exceptions:
(1) Dimming ballasts and
(2) Ballasts for circline and compact fluorescent lamps and low-wattage HID lamps not over 100 W.
402.4.1.2 Fenestration The design of the fenestration shall meet the criteria of table 402.4.1.2. When the fenestration columns labeled "perimeter Daylighting" are used,
automatic daylighting controls shall be installed in the perimeter daylighted zones of the building. These daylighting controls shall be capable of reducing electric lighting power to
at least 50% of full power. Only those shading or lighting controls for perimeter daylighting that are shown on the plans shall be considered. The column labeled "VLT > = SC" shall be used only
when the shading coefficient of the glass is less than its visible light transmittance.
| TABLE 402.3.1(B) MAX. EXEMPT SKYLIGHT AREA AS % OF ROOF AREA |
Visible Light
Transmittance (VLT) |
Light Level
Ft. Candles |
Range of Lighting Power Densities |
| <1.00 |
1.00 - 1.50 |
1.51 - 2.00 |
>2.00 |
| 0.75 |
30 |
2.3 |
3.4 |
4.5 |
5.6 |
| 50 |
2.5 |
4.0 |
5.5 |
7.0 |
| 70 |
2.8 |
4.6 |
6.4 |
8.2 |
| 0.50 |
30 |
3.6 |
5.1 |
6.6 |
8.1 |
| 50 |
3.9 |
6.0 |
8.1 |
10.2 |
| 70 |
4.2 |
6.9 |
9.6 |
12.3 |
402.4.2.2 Lighting Power Density (LIGHTS) The lighting power density used in the ENVSTD21 computer program shall use the actual lighting power density from the
building plans and specifications or the appropriate value from Tables 401.3.2a or 401.3.2b, c, or d if the lighting system design is not included in the building permit application.
402.4.2.3 Daylighting Control Credit Fraction (DLCF) When the daylighting control credit fraction is other than zero, automatic daylighting controls shall be installed in the appropriate
perimeter zone(s) of the building to justify the credit. The building permit application shall include the lighting design.
403.2.7.1 Automatic Setback o Shutdown Controls HVAC systems shall be equipped with automatic controls capable of accomplishing a reduction of energy use through
control setback or equipment shutdown. Exceptions:
(1) Systems serving areas expected to operate continuously or
(2) equipment with full-load demands not exceeding 2 kW controlled by readily accessible, manual off-hour controls.
ASHRAE 90.1 - 1999
General Lighting Requirements
Automatic Shut-off Controls
Space Control
Exterior Lighting Control
Additional Control
Tandem Wiring
Interior Lighting Density Overview
4.1.2.2.5 Lighting Alterations. The replacement of lighting systems in any building space shall comply with the lighting power density requirements of
Section 9 applicable to that space. New lighting systems shall comply with the applicable lighting power density requirements of section 9. Any new control devices as a direct
replacement of existing control devices shall comply with the specific requirements of Sections 9.2.1.2(a) and 9.2.1.2(c)
Exception to 4.1.2.2.5: Alterations that replace less than 50% of the luminaires in a space need not comply with these
requiremnts provided that such alterations do not increase the installed interior lighting power.
5.2.1.3 Recessed Equipment: Lighting fixtures; heating, ventilating, and air-conditioning equipment, including wall heaters, ducts, and plenums; and other
equipment shall not be recessed in such a manner as to affect the insulation thickness unless:
(a) the total combined area affected (including necessary clearances) is less than one percent of the opaque area of the assembly, or
(b) the entire roof, wall, or floor us covered with insulation to the full depth required, or
(c) the effects of reduced insulation are included in calculations using an area-weighted average method and compressed insulation values obtained from Table A-24.
In all cases, air leakage through or around the recessed equipment to the conditioned space shall be limited in accordance with 5.2.3.1.
9. LIGHTING (back to top)
9.1 General
Lighting systems and equipment shall comply with the requirements of 9.2 and 9.3. This section shall apply to the following:
(a) interior spaces of buildings;
(b) exterior building features, including facades, illuminated roofs, architectural features, entrances, exits, loading docks and illuminated canopies; and
(c) exterior building grounds lighting provided through the building's electrical service.
Exceptions to 9.1:
(a) emergency lighting that is automatically off during normal building operation,
(b) lighting within living units,
(c) lighting that is specifically designated as required by a health or life safety statue, ordinance or regulation,
(d) decorative gas lighting systems.
9.2 Mandatory Provisions
9.2.1 Lighting Control
(back to top)
9.2.1.1 Automatic Lighting Shutoff. Interior lighting in buildings larger than 5000 ft. ² shall be controlled with an automatic control device to shut off building lighting in all
spaces. This automatic control device shall function on either
(a) a time-of-day operated control device that turns lighting off at specific programmed times - an independent program schedule shall be provided for areas of no more than 25,000 ft.² but
not more than one floor - or
(b) an occupant sensor that shall turn lighting off within 30 minutes of an occupant leaving a space or
(c) by occupant intervention.
Exception to 9.2.1.1: Lighting intended for 24-hour operation shall not require an automatic control device .
(back to top)
9.2.1.2 Space Control. Each space enclosed by ceiling-height partitions shall have at least one control device to independently control the general lighting within the space. Each control
device shall be activated either manually by an occupant or automatically by sensing an occupant. Each control device shall
control a maximum of 2500 ft.² area for a space 10,000 ft.² or less and a maximum of 10,000 ft.²,
be capable of overriding the shutoff control required in 9.2.1.1 for no more than four hours, and
be readily accessibly and located so the occupant can see the controlled lighting.
Exception to 9.2.1.2: Remote location shall be permitted for reasons of safety or security when the remote control device has an indicator pilot light as part of or next to the control
device and it shall be clearly labeled to identify the controlled lighting.
(back to top)
9.2.1.3 Exterior Lighting Control. Lighting for all exterior applications not exempted in 9.1 and 9.3.2. shall be controlled by a photosensor or astronomical time switch that is capable of
automatically turning off the exterior lighting when sufficient daylight is available or the lighting is not required.
Exception to 9.2.1.3: Lighting for covered vehicle entrances or exits from buildings or parking structures where required for safety, security or eye adaptation.
(back to top)
9.2.1.4 Additional Control.
(a) Display/Accent Lighting—display or accent lighting shall have a separate control device.
(b) Case Lighting—lighting in cases used for display purposes shall have a separate control device.
(c) Hotel and Motel Guest Room Lighting—hotel and motel guest rooms and guest suites shall have a master control device at the main room entry that controls all permanently
installed luminaries and switched receptacles
(d) Task Lighting—supplemental task lighting, including permanently installed undershelf or undercabinet lighting, shall have a control device integral to the luminaires or be
controlled by wall-mounted control device provided the control device is readily accessible and located so that the occupant can see the controlled lighting.
(e) Nonvisual Lighting—lighting for nonvisual applications, such as plant growth and food warming, shall have a separate control device .
(f) Demonstration Lighting—lighting equipment that is for sale or for demonstrations in lighting education shall have a separate control device.
(back to top)
9.2.2 Tandem Wiring. Luminaires designed for use with one or three linear fluorescent lamps greater than 30 W each shall use two-lamp tandem-wired ballasts in place of single-lamp ballasts
when two or more luminaires are in the same space and on the same control device.
Exceptions to 9.2.2:
(a) Recessed luminaires more than 10 ft apart measured center to center.
(b) Surface-mounted or pendant luminaires that are not continuous.
(c) Luminaires using single-lamp high-frequency electronic ballasts.
(d) Luminaires using three-lamp high-frequency electronic or three-lamp electromagnetic ballasts.
(e) Luminaires on emergency circuits.
(f) Luminaires with no available pair.
9.2.3 Exit Signs. Exit sign luminaires operating at greater than 20 watts shall have a minimum source efficacy of 35 lm/W.
(back to top)
9.2.4 Installed Interior Lighting Power. The installed interior lighting power shall include all power used by the luminaires, including lamps , ballasts , current regulators and control
devices except as specifically exempted in 9.3.1.
Exception to 9.2.4: If two or more independently operating lighting systems in a space are capable of being controlled to prevent simultaneous user operation, the installed interior
lighting power shall be based solely on the lighting system with the highest wattage.
9.3 Prescriptive Path
9.3.1 Interior Lighting Power. The interior lighting power allowance for a building or a separately metered or permitted portion of a building shall be determined by either the building
area method described in 9.3.1.1 or the space-by space method described in 9.3.1.2. Trade-offs of interior lighting power allowance among portions of the building for which a different method of
calculation has been used are not permitted. The installed interior lighting power identified in accordance with 9.2.4 shall not exceed the interior lighting power allowance developed in
accordance with 9.3.1.1 or 9.3.1.2.
Exceptions to 9.3.1: The following lighting equipment and applications shall not be considered when determining the interior lighting power allowance developed in accordance with 9.3.1.1
or 9.3.1.2, nor shall the wattage for such lighting be included in the installed interior lighting power identified in accordance with 9.2.4. However, any such lighting shall not be exempt unless
it is an addition to general lighting and is controlled by an independent control device.
(a) Display or accent lighting that is an essential element for the function performed in galleries, museums, and monuments.
(b) Lighting that is integral to equipment or instrumentation and is installed by its manufacturer.
(c) Lighting specifically designed for use only during medical or dental procedures and lighting integral to medical equipment.
(d) Lighting integral to both open and glass enclosed refrigerator and freezer cases.
(e) Lighting integral to food warming and food preparation equipment.
(f) Lighting for plant growth or maintenance.
(g) Lighting in spaces specifically designed for use by the visually impaired.
(h) Lighting in retail display windows, provided the display area is enclosed by ceiling-height partitions.
(i) Lighting in interior spaces that have been specifically designated as a registered interior historic landmark.
(j) Lighting that is an integral part of advertising or directional sign age.
(k) Exit signs.
(l) Lighting that is for sale or lighting educational demonstration systems.
(m) Lighting for theatrical purposes, including performance, stage, and film and video production.
(n) Athletic playing areas with permanent facilities for television broadcasting.
(o) Casino gaming areas.
9.3.1.1 Building Area Method of Calculating Interior Lighting Power Allowance. The building area method shall be used only in the following cases: (a) projects involving the entire
building or (b) projects involving a single, independent, and separate occupancy in a multi-occupancy building. Use the following steps to determine the interior lighting power allowance by the
building area method:
(a) Determine the appropriate building type from Table 9.3.1.1 and the allowed lighting power density (watts per unit area) from the building area method column. For building types not listed,
selection of a reasonably equivalent type shall be permitted.
(b) Determine the gross lighted floor area (square feet) of the building.
(c) The interior lighting power allowance is the product of the lighted floor area of the building times the lighting power density.
9.3.1.2 Space-by-Space Method of Calculating Interior Lighting Power Allowance. Use the following steps to determine the interior lighting power allowance by the space by-space method:
(a) Determine the appropriate building type from Table 9.3.1.2. For building types not listed, selection of a reasonably equivalent type shall be permitted.
(b) For each space enclosed by partitions 80% or greater than ceiling height, determine the gross interior floor area by measuring to the center of the partition wall. Include the floor area of
balconies or other projections. Retail spaces do not have to comply with the 80% partition height requirements.
(c) Determine the interior lighting power allowance by using the columns designated space-by-space method in Table 9.3.1.2. Multiply the floor area(s) of the space(s) times the allowed lighting
power density for the space type that most closely represents the proposed use of the space(s). The product is the lighting power allowance for the space(s). For space types not listed, selection
of a reasonable equivalent category shall be permitted.
(d) The interior lighting power allowance is the sum of lighting power allowances of all spaces. Trade-offs among spaces are permitted provided that the total installed interior lighting power
does not exceed the interior lighting power allowance.
Additional Interior Lighting Power. An increase in the interior lighting power allowance is allowed when using the space-by-space method for specific space functions as noted in Table
9.3.1.2. In all such spaces in which an additional lighting power allowance is taken, the additional power shall be allowed only if the specified lighting is installed. Additional power shall be
used only for the specified luminaires and shall not be used for any other purpose or in any other space.
An increase in the interior lighting power allowance for space types noted in Table 9.3.1.2 as eligible for additional interior lighting power allowance is permitted in the following cases:
(a) For spaces in which lighting is specified to be installed in addition to the general lighting for the purpose of decorative appearance, such as chandelier-type lumi-naries or sconces or for
highlighting art or exhibits,provided that the additional lighting power shall not exceed 1.0 W/ft² of such spaces.
(b) For spaces in which lighting is specified to be installed to meet the requirements of visual display terminals as the primary viewing task, provided that the additional lighting power shall
not exceed 0.35 W/ft² of such spaces and that the specified luminaire meets requirements for use in such spaces. Maximum average luminance measured from the vertical in candelas per square
foot of not more than 80 cd/ft² at 65 degrees, 33cd/ft² at 75 degrees, and 17 cd/ft² at 85 to 90 degrees.
(c) For lighting equipment installed in retail spaces that is specifically designed and directed to highlight merchandise, provided that the additional lighting power shall not exceed(1)1.6
W/ft² or(2)3.9 W/ft² for displaying and selling fine merchandise (such as jewelry, fine apparel and accessories, china and silver) and in art galleries and similar spaces where detailed
display and examination of merchandise is important.
TABLE 9.3.1.1
Lighting Power Densities Using
the Building Area Method
| Building Type |
Lighting Power Density
(W/ft²) |
| Automotive Facility |
1.5 |
| Convention Center |
1.4 |
| Court House |
1.4 |
| Dining: Bar Lounge/Leisure |
1.5 |
| Dining: Cafeteria/Fast Food |
1.8 |
| Dining: Family |
1.9 |
| Dormitory |
1.5 |
| Exercise Center |
1.4 |
| Gymnasium |
1.7 |
| Hospital/Health Care |
1.6 |
| Hotel |
1.7 |
| Library |
1.5 |
| Manufacturing Facility |
2.2 |
| Motel |
2.0 |
| Motion Picture Theater |
1.6 |
| Multi-Family |
1.0 |
| Museum/td> |
1.6 |
| Office |
1.3 |
| Parking Garage |
0.3 |
| Penitentiary |
1.2 |
| Performing Arts Theater |
1.5 |
| Police/Fire Station |
1.3 |
| Post Office |
1.6 |
| Religious Building |
2.2 |
| Retail |
1.9 |
| School/University |
1.5 |
| Sports Arena |
1.5 |
| Town Hall |
1.4 |
| Transportation |
1.2 |
| Warehouse |
1.2 |
| Workshop |
1.7 |
9.3.2 Exterior Building Lighting Power. The exterior lighting power allowance is the sum of lighting power allowances for all of the applicable exterior applications permitted,other than
building facades, provided that the total installed exterior lighting power does not exceed the exterior lighting power allowance. Exterior lighting for all applications(except those included in
the exceptions to 9.1 and 9.3.2) shall comply with the requirements of 9.2.6.
Exceptions to 9.3.2: Lighting used for the following exterior applications is exempt when equipped with an independent control device:
(a) specialized signal, directional, and marker lighting associated with transportation;
(b) lighting used to highlight features of public monuments and registered historic landmark structures or buildings; and
(c) lighting that is integral to advertising sign age.
TABLE 9.3.2
Lighting Power Limits for Building Exteriors
| Applications |
Power Limits |
| Building entrance with canopy or free standing canopy |
3 W/ft² of canopied area |
| Building entrance without canopy |
33 W/lin ft of door width |
| Building exit |
20 W/lin ft of door width |
| Building facades |
0.25 W/ft²of illuminated facade area |
11.3.8 Lighting. Lighting power in the proposed design shall be determined as follows:
(a) Where a complete lighting system exists, the actual lighting power shall be used in the model.
(b) Where a lighting system has been designed, lighting power shall be determined in accordance with 9.3.
(c) Where no lighting exists or is specified, lighting power shall be determined in accordance with the Building Area Method for the appropriate building type.
11.4.5 Lighting. Lighting power in the budget building design shall be determined using the same categorization procedure (building area or space function) and
categories as the proposed design with lighting power set equal to the maxi-mum allowed for the corresponding method and category in9.3. Lighting controls shall be the minimum required.
TABLE C3.5
VLT Factor for the Base Envelope Design
| Climate Bin |
Vertical Fenestration |
Glass Skylights |
Plastic Skylights |
| 1 |
1.00 |
1.27 |
1.20 |
| 2 |
1.00 |
1.27 |
1.20 |
| 3 |
1.00 |
1.27 |
1.20 |
| 4 |
1.00 |
1.27 |
1.20 |
| 5 |
1.00 |
1.27 |
1.20 |
| 6 |
1.00 |
1.27 |
1.20 |
| 7 |
1.00 |
1.27 |
1.20 |
| 8 |
1.00 |
1.27 |
1.20 |
| 9 |
1.00 |
1.27 |
1.20 |
| 10 |
1.27 |
1.27 |
1.20 |
| 11 |
1.27 |
1.27 |
1.20 |
| 12 |
1.00 |
1.27 |
1.20 |
| 13 |
1.27 |
1.27 |
1.20 |
| 14 |
1.27 |
1.27 |
1.20 |
| 15 |
1.27 |
1.27 |
1.20 |
| 16 |
1.27 |
1.27 |
1.20 |
| 17 |
1.27 |
1.27 |
1.20 |
| 18 |
1.27 |
1.27 |
1.20 |
| 19 |
1.27 |
1.27 |
1.20 |
| 20 |
1.00 |
1.00 |
1.20 |
| 21 |
1.00 |
1.00 |
1.20 |
| 22 |
1.00 |
1.00 |
1.20 |
| 23 |
1.00 |
1.00 |
1.20 |
| 24 |
1.00 |
1.00 |
1.20 |
| 25 |
1.00 |
1.00 |
1.20 |
| 26 |
1.00 |
1.00 |
1.20 |
C5.4 The electrical systems shall be the same for both the base envelope design and the proposed design. The lighting power density shall be 1.20 W/ft² for nonresidential conditioned
spaces, 1.00 W/ft² for residential conditioned spaces,and 0.50 W/ft² for semi heated spaces. The equipment power density shall be 0.75 W/ft² for nonresidential conditioned spaces,
0.25 W/ft² for residential conditioned spaces, and0.25 W/ft² for semi heated spaces. Continuous daylight dim-ming shall be assumed in all spaces and be activated at 50 fc for
nonresidential conditioned spaces and residential conditioned spaces and 30 fc for semi heated spaces.
C5.5 Surface reflectance's for day lighting calculations shall be 80% for ceilings, 50% for walls, and 20% for floors.
C5.6 Envelope performance factor is defined in the following equation.
C6.2 Envelope Performance Factor. The envelope performance factor (EPF) of a building shall be calculated using Equation C-2.
C6.4 Lighting. The lighting term for each zone in the building as defined in C4 shall be calculated using Equation C-4.
INTERPRETATION IC 90.1-1999-1 OF
ASHRAE/IESNA STANDARD 90.1-1999
Energy Standard for Buildings Except Low-Rise Residential Buildings
February 4, 2000
Request from: Charles Eley, Eley Associates, 142 Minna Street, San Francisco, California 94105
Reference: This request for interpretation refers to the requirements presented in ASHRAE/IESNA Standard 90.1-1999, Section 9.3.2, relating to the exterior lighting power allowance.
Background: Section 9.3.2 has lighting power limits for exterior building lighting. Table 9.3.2 has limits for building entrances with a canopy, building entrances without a canopy,
building exits and illuminated building facades. For a single building, the standard permits trade-offs between these four applications.
Interpretation: For multi-building projects, exterior lighting power can be traded off between buildings. Each building does not have to separately meet its exterior lighting power
allowance.
Question: Is this interpretation correct?
Answer: Yes. The exterior lighting power allowance of a multi-building project is the sum of lighting power allowances for the applicable exterior entrances (with and without canopies)
and exits of all buildings.
Comments: The designer is provided with additional flexibility for relatively minor lighting loads without changing the total amount of exterior power allowance for the total project.
Building facades are not part of the exterior lighting power allowance. Building facade lighting power is “use-it or lose-it”.
ASHRAE 90.1 - 2001
9.2.1 Lighting Control
TABLE 9.3.1.1 - Lighting Power Densities - Building Area Method
ASHRAE 90.1 1999 addendum
ASHRAE 90.1 2001 addendum
9.2.1 Lighting Control
9.2.1.1 Automatic Lighting Shutoff. Interior lighting in buildings larger than 5000 ft² shall be controlled with an automatic control device to shut off
building lighting in all spaces. This automatic control device shall function on either
- a scheduled basis using a time-of-day operated control device that turns lighting off at specific programmed times–an independent program schedule shall be provided for areas of no more
than 25,000 ft² but not more than one floor–or
- an occupant sensor that shall turn lighting off within 30 minutes of an occupant leaving a space–or
- a signal from another control or alarm system that indicates the area is unoccupied.
Exception to 9.2.1.1: Lighting intended for 24-hour operation shall not require an automatic control device.
9.2.1.2 Space Control. Each space enclosed by ceiling height partitions shall have at least one control device to independently control the general lighting within the space. Each control
device shall be activated either manually by an occupant or automatically by sensing an occupant. Each control device shall
- control a maximum of 2500 ft² area for a space 10,000 ft² or less and a maximum of 10,000 ft² area for a space greater than 10,000 ft²,
- be capable of overriding the shutoff control required in 9.2.1.1 for no more than four hours, and
- be readily accessible and located so the occupant can see the controlled lighting.
Exception to 9.2.1.2: Remote location shall be permitted for reasons of safety or security when the remote control device has an indicator pilot
light as part of or next to the control device and it shall be clearly labeled to identify the controlled lighting.
9.2.1.3 Exterior Lighting Control. Lighting for all exterior applications not exempted in 9.1 and 9.3.2 shall be controlled by a photo sensor or astronomical time switch that is capable of
automatically turning off the exterior lighting when sufficient daylight is available or the lighting is not required.
Exception to 9.2.1.3: Lighting for covered vehicle entrances or exits from buildings or parking structures where required for safety, security, or
eye adaptation.
9.2.1.4 Additional Control.
- Display/Accent Lighting display or accent lighting shall have a separate control device.
- Case Lighting–lighting in cases used for display purposes shall have a separate control device.
- Hotel and Motel Guest Room Lighting–hotel and motel guest rooms and guest suites shall have a master control device at the main room entry that controls all permanently installed
luminaires and switched receptacles.
- Task Lighting–supplemental task lighting, including permanently installed under shelf or under cabinet lighting, shall have a control device integral to the luminaires or be
controlled by a wall-mounted control device provided the control device is readily accessible and located so that the occupant can see the controlled lighting
- Nonvisual Lighting–lighting for nonvisual applications, such as plant growth and food warming, shall have a separate control device.
- Demonstration Lighting–lighting equipment that is for sale or for demonstrations in lighting education shall have a separate control device.
TABLE 9.3.1.1
Lighting Power Densities Using
the Building Area Method
| Building Area Typea |
Lighting Power Density
(W/ft²) |
| Automotive Facility |
1.5 |
| Convention Center |
1.4 |
| Court House |
1.4 |
| Dining: Bar Lounge/Leisure |
1.5 |
| Dining: Cafeteria/Fast Food |
1.8 |
| Dining: Family |
1.9 |
| Dormitory |
1.5 |
| Exercise Center |
1.4 |
| Gymnasium |
1.7 |
| Hospital/Health Care |
1.6 |
| Hotel |
1.7 |
| Library |
1.5 |
| Manufacturing Facility |
2.2 |
| Motel |
2.0 |
| Motion Picture Theater |
1.6 |
| Multi-Family |
1.0 |
| Museum |
1.6 |
| Office |
1.3 |
| Parking Garage |
0.3 |
| Penitentiary |
1.2 |
| Performing Arts Theater |
1.5 |
| Police/Fire Station |
1.3 |
| Post Office |
1.6 |
| Religious Building |
2.2 |
| Retail |
1.9 |
| School/University |
1.5 |
| Sports Arena |
1.5 |
| Town Hall |
1.4 |
| Transportation |
1.2 |
| Warehouse |
1.2 |
| Workshop |
1.7 |
a In cases where both general building area type and a specific building area type are listed, the specific building area type shall apply.
9.2.2 Tandem Wiring. Luminaires designed for use with one or three linear fluorescent lamps greater than 30 W each shall use two-lamp tandem-wired ballasts in
place of single-lamp ballasts when two or more luminaires are in the same space and on the same control device.
Exceptions to 9.2.2:
(a) Recessed luminaires more than 10 ft apart measured center.
(b) Surface-mounted or pendant luminaires that are not continuous.
(c) Luminaires using single-lamdivhigh-frequency electronic ballasts.
(d) Luminaires using three-lamdivhigh-frequency electronic or three-lamp electromagnetic ballasts.
(e) Luminaires on emergency circuits.
(f) Luminaires with no available pair.
9.2.3 Exit Signs. Exit sign luminaires operating at greater than 20 watts shall have a minimum source efficacy of 35 lm/W.
9.2.4 Installed Interior Lighting Power. The installed interior lighting power shall include all power used by the luminaires, including lamps, ballasts, current regulators, and control devices
except as specifically exempted in 9.3.1.
Exception to 9.2.4: If two or more independently operating lighting systems in a space are capable of being controlled to prevent simultaneous user
operation, the installed interior lighting power shall be based solely on the lighting system with the highest wattage.
9.2.5 Luminaire Wattage.Luminaire wattage incorporated into the installed interior lighting power shall be determined in accordance with the following
criteria:
- The wattage of incandescent or tungsten-halogen luminaires with medium screw base sockets and not containing permanently installed ballasts shall be the maximum labeled wattage of the
luminaire.
- The wattage of luminaires with permanently installed or remote ballasts or transformers shall be the operating input wattage of the maximum lamp/auxiliary combination based on values from the
auxiliary manufacturer’s literature or recognized testing laboratories.
- The wattage of line-voltage lighting track and plug-in busway that allow the addition and/or relocation of luminaires without altering the wiring of the system shall be the specified wattage
of the luminaires included in the system with a minimum of 30 W/lin ft.
- The wattage of low-voltage lighting track, cable conductor, rail conductor, and other flexible lighting systems that allow the addition and/or relocation of luminaires without altering the
wiring of the system shall be the specified wattage of the transformer supplying the system.
- The wattage of all other miscellaneous lighting equipment shall be the specified wattage of the lighting equipment.
9.2.6 Exterior Building Grounds Lighting. All exterior building grounds luminaires that operate at greater than 100 watts shall contain lamps having a minimum efficacy of 60 lm/W unless the
luminaire is controlled by a motion sensor or qualifies for one of the exceptions under 9.1 or 9.3.2.
9.3 Prescriptive Path
9.3.1 Interior Lighting Power. The interior lighting power allowance for a building or a separately metered or permitted portion of a building shall be determined
by either the building area method described in 9.3.1.1 or the space-by space method described in 9.3.1.2. Trade-offs of interior lighting power allowance among portions of the building for which a
different method of calculation has been used are not permitted. The installed interior lighting power identified in accordance with 9.2.4 shall not exceed the interior lighting power allowance
developed in accordance with 9.3.1.1 or 9.3.1.2.
Exceptions to 9.3.1: The following lighting equipment and applications shall not be considered when determining the interior lighting power
allowance developed in accordance with 9.3.1.1 or 9.3.1.2, nor shall the wattage for such lighting be included in the installed interior lighting power identified in accordance with 9.2.4. However,
any such lighting shall not be exempt unless it is an addition to general lighting and is controlled by an independent control device.
(a) Display or accent lighting that is an essential element for the function performed in galleries, museums, and monuments.
(b) Lighting that is integral to equipment or instrumentation and is installed by its manufacturer.
(c) Lighting specifically designed for use only during medical or dental procedures and lighting integral to medical equipment.
(d) Lighting integral to both open and glass enclosed refrigerator and freezer cases.
(e) Lighting integral to food warming and food preparation equipment.
(f) Lighting for plant growth or maintenance.
(g) Lighting in spaces specifically designed for use by the visually impaired.
(h) Lighting in retail display windows, provided the display area is enclosed by ceiling-height partitions.
(i) Lighting in interior spaces that have been specifically designated as a registered interior historic landmark.
(j) Lighting that is an integral part of advertising or directional signage.
(k) Exit signs.
(l) Lighting that is for sale or lighting educational demonstration systems.
(m) Lighting for theatrical purposes, including performance, stage, and film and video production.
(n) Athletic playing areas with permanent facilities for television broadcasting.
(o) Casino gaming areas.
9.3.1.1 Building Area Method of Calculating Interior Lighting Power Allowance. Use the following steps to determine the interior lighting power allowance by the
building area method:
- Determine the appropriate building area type from Table 9.3.1.1 and the allowed lighting power density (watts per unit area) from the building area method column. For building area types not
listed, selection of a reasonably equivalent type shall be permitted.
- Determine the gross lighted floor area (square feet) of the building area type.
- Multiply the gross lighted floor areas of the building area type(s) times the lighting power density.
- The interior lighting power allowance for the building is the sum of the lighting power allowances of all building area types. Trade-offs among building area types are permitted provided that
the total installed interior lighting power does not exceed the interior lighting power allowance.
9.3.1.2 Space-by-Space Method of Calculating Interior Lighting Power Allowance. Use the following steps to determine the interior lighting power allowance by the
space-by-space method:
- Determine the appropriate building type from Table 9.3.1.2. For building types not listed, selection of a reasonably equivalent type shall be permitted.
- For each space enclosed by partitions 80% or greater than ceiling height, determine the gross interior floor area by measuring to the center of the partition wall. Include the floor area of
balconies or other projections. Retail spaces do not have to comply with the 80% partition height requirements.
- Determine the interior lighting power allowance by using the columns designated space-by-space method in Table 9.3.1.2. Multiply the floor area(s) of the space(s) times the allowed lighting
power density for the space type that most closely represents the proposed use of the space(s). The product is the lighting power allowance for the space(s). For space types not listed, selection
of a reasonable equivalent category shall be permitted.
- The interior lighting power allowance is the sum of lighting power allowances of all spaces. Trade-offs among spaces are permitted provided that the total installed interior lighting power
does not exceed the interior lighting power allowance.
9.3.1.2.1 Additional Interior Lighting Power. When using the space-by-space method, an increase in the interior lighting power allowance is allowed for specific
lighting functions. Additional power shall be allowed only if the specified lighting is installed, shall be used only for the specified luminaires, and shall not be used for any other purpose or in
any other space.
An increase in the interior lighting power allowance is permitted in the following cases:
- For spaces in which lighting is specified to be installed in addition to the general lighting for the purpose of decorative appearance, such as chandelier-type luminaries or sconces or for
highlighting art or exhibits, provided that the additional lighting power shall not exceed 1.0 W/ft² of such spaces.
- For spaces in which lighting is specified to be installed to meet the requirements of visual display terminals as the primary viewing task, provided that the additional lighting power shall
not exceed 0.35 W/ft² of such spaces and that the specified luminaire meets requirements for use in such spaces. Maximum average luminance measured from the vertical in candelas per square
foot of not more than 80 cd/ft² at 65 degrees, 33 cd/ft² at 75 degrees, and 17 cd/ft² at 85 to 90 degrees.
- For lighting equipment installed in retail spaces that is specifically designed and directed to highlight merchandise, provided that the additional lighting power shall not exceed
- 1.6 W/ft² times the area of specific display or
- 3.9 W/ft² times the area of specific display for valuable merchandise, such as jewelry, fine apparel and accessories, china and silver, art, and similar items, where detailed display
and examination of merchandise are important.
TABLE 9.3.2
Lighting Power Limits for Building Exteriors
| Applications |
Power Limits |
| Building entrance with canopy or free standing canopy |
3 W/ft² of canopied area |
| Building entrance without canopy |
33 W/lin ft of door width |
| Building exit |
20 W/lin ft of door width |
9.3.2 Exterior Building Lighting Power. The exterior building facade lighting power shall not exceed 0.25 W/ft² of the illuminated area. The exterior lighting
power allowance for all other exterior building applications is the sum of the lighting power limits permitted and specified in Table 9.3.2 for these applications. Exterior lighting for all
applications (except those included in the exceptions to 9.1 and 9.3.2) shall comply with the requirements of 9.2.6.
Exceptions to 9.3.2: Lighting used for the following exterior applications is exempt when equipped with an independent control device:
(a) specialized signal, directional, and marker lighting associated with transportation;
(b) lighting used to highlight features of public monuments and registered historic landmark structures or buildings; and
(c) lighting that is integral to advertising signage.
…
11.3.8 Lighting. Lighting power in the proposed design shall be determined as follows:
- Where a complete lighting system exists, the actual lighting power shall be used in the model.
- Where a lighting system has been designed, lighting power shall be determined in accordance with 9.3.
- Where no lighting exists or is specified, lighting power shall be determined in accordance with the Building Area Method for the appropriate building type.
…
11.4.5 Lighting. Lighting power in the budget building design shall be determined using the same categorization procedure (building area or space function) and categories as the proposed design
with lighting power set equal to the maximum allowed for the corresponding method and category in 9.3. Lighting controls shall be the minimum required.
…
C5.4 The electrical systems shall be the same for both the base envelope design and the proposed design. The lighting power density shall be 1.20 W/ft² for nonresidential conditioned
spaces, 1.00 W/ft² for residential conditioned spaces, and 0.50 W/ft² for semiheated spaces. The equipment power density shall be 0.75 W/ft² for nonresidential conditioned spaces,
0.25 W/ft² for residential conditioned spaces, and 0.25 W/ft² for semiheated spaces. Continuous daylight dimming shall be assumed in all spaces and be activated at 50 fc for
nonresidential conditioned spaces and residential conditioned spaces and 30 fc for semiheated spaces.
TABLE C6.6
Coefficients for Calculating Kd
| Coefficient |
Skylight |
Vertical Fenestration |
| Φ1 |
0.589 |
0.737 |
| Φ2 |
5.18E-07 |
-3.17E-04 |
| Φ3 |
-220 |
-24.71 |
| Φ4 |
2.29 |
0.234 |
TABLE F-1
Addenda to ANSI/ASHRAE/IESNA Standard 90.1-1999; Changes Identified
Addenda to
90.1-1999 |
Sections Affected |
Description of Changesa |
| 90.1v |
9. Lighting |
In 9.2.1.1, Automatic Lighting Shutoff, the term “occupant intervention” is vague and needed clarification. |
| 90.1w |
9. Lighting |
This change to 9.3.1.2, Space-by-Space Method of Calculating Interior Lighting Power Allowance, clarifies the intended use of this additional interior lighting allowance. |
| 90.1y |
9. Lighting |
This addendum clarifies the definition of “General Low Bay” and “General High Bay” under the heading of Industrial Buildings, Table 9.3.1.2, Lighting Power Densities
Using the Space-by-Space Method. |
| 90.1z |
9. Lighting |
This change to 9.3.2, Exterior Building Lighting Power, and Table 9.3.2, Lighting Power Limits for Building Exteriors, clarifies the language and intent of exterior building lighting
power. |
| 90.1aa |
8. Power |
Change to 8.2.1.1, Feeders, and 8.2.1.2, Branch Circuits, specifies that connection load is not always the sizing method used in electrical design. |
| 90.1ab |
9. Lighting |
Change to 9.3, Prescriptive Path, and Table 9.3.1.2, Space-by-Space Method of Calculating Interior Lighting Power Allowance, clarifies that the additional power allowances apply to any
lighted area that meets the criteria. |
| 90.1ah |
9. Lighting |
Change to 9.3.1.1 to allow building area lighting power allowance method to be used for all buildings. |
| 90.1ai |
9. Lighting |
Change to 9.3.1.1, adding footnote to Table 9.3.1.1 to indicate specific building types apply. |
a These descriptions may not be complete and are provided for information only.
G3.8 Lighting. Lighting power in the proposed design shall be determined as follows:
(a) Where a complete lighting system exists, the actual lighting power shall be used in the model.
(b) Where a lighting system has been designed, lighting power shall be determined in accordance with 9.2.4 and9.2.5.
(c) Where lighting neither exists nor is specified, lighting power shall be determined in accordance with the building area method for the appropriate building type.
(d) Lighting system power shall include all lighting system components shown or provided for on the plans (including lamps and ballasts and task and furniture-mounted fixtures).
Exception to G3.8 (d): For multifamily living units, hotel/motel guest rooms, and other spaces in which lighting systems are connected via
receptacle sand are not shown or provided for on building plans, assume identical lighting power for the proposed and baseline building designs in the simulations, but exclude these loads when
calculating the baseline building performance and proposed building performance.
(e) Lighting power for parking garages and building facades shall be modeled.
(f) Credit may be taken for the use of automatic controls for daylight utilization but only if their operation is either modeled directly in the building simulation or modeled in the building
simulation through schedule adjustments determined by a separate day lighting analysis approved by the rating authority.
(g) For automatic lighting controls in addition to those required for minimum code compliance under 9.2, credit may be taken for automatically controlled systems by reducing the connected
lighting power by the applicable percentages listed in Table G3.8. Alternatively, credit may be taken for these devices by modifying the lighting schedules used for the proposed design, provided
that credible technical documentation for the modifications are provided to the rating authority.
TABLE G3.8
Power Adjustment Percentages for Automatic Lighting Controls
| Automatic Control Devices(s) |
Non 24 h &
<=5,000 ft² (460 m²) |
All other |
| (1) Programmable timing control |
10% |
0% |
| (2) Occupancy sensor |
15% |
10% |
| (3) Occupancy sensor and programmable timing control |
15% |
10% |
Note:The 5,000ft⊃ (460 m²) condition pertains to the total floor area of the building.
G4.4 Baseline Lighting Systems. Lighting power in the baseline building design shall be determined using the same categorization procedure (Building Area or Space Function) and categories as the
proposed design with lighting power set equal to the maximum allowed for the corresponding method and category in 9.3. No automatic lighting controls (e.g., programmable controls or automatic
controls for daylight utilization) shall be modeled in the baseline building design because the lighting schedules used are understood to reflect the mandatory control requirements in this
standard.
ADDENDUM g to 90.1-2001 (I-P and SI EDITIONS)
-
Revise Table 9.3.1.1 as shown to incorporate revised whole building LPD values and split the previous hospital/health care category into two separate categories. The revised LPD values
reflect current light source efficiency data, recent research work on light loss factors, and the latest IESNA light level recommendations.
I-P TABLES:
TABLE 9.3.1.1,
Lighting Power Densities Using
the Building Area Method
| Building Area Type |
Lighting Power Density (W/ft²) |
| Automotive Facility |
0.9 |
| Convention Center |
1.2 |
| Court House |
1.2 |
| Dining: Bar Lounge/Leisure |
1.3 |
| Dining: Cafeteria/Fast Food |
1.4 |
| Dining: Family |
1.6 |
| Dormitory |
1.0 |
| Exercise Center |
1.0 |
| Gymnasium |
1.1 |
| Healthcare-Clinic |
1.0 |
| Hospital |
1.2 |
| Hotel |
1.0 |
| Library |
1.3 |
| Manufacturing Facility |
1.3 |
| Motel |
1.0 |
| Motion Picture Theatre |
1.2 |
| Multi-Family |
0.7 |
| Museum |
1.1 |
| Office |
1.0 |
| Parking Garage |
0.3 |
| Penitentiary |
1.0 |
| Performing Arts Theatre |
1.6 |
| Police/Fire Station |
1.0 |
| Post Office |
1.1 |
| Religious Building |
1.3 |
| Retail |
1.5 |
| School/University |
1.2 |
| Sports Arena |
1.1 |
| Town Hall |
1.1 |
| Transportation |
1.0 |
| Warehouse |
0.8 |
| Workshop |
1.4 |
a In cases where both general building area type and a specific building area type are listed, the specific building area type shall apply.
-
Replace Table 9.3.1.2 with the following new table to incorporate revised space-by-space LPD values and provide a table format that includes the same space categories as the previous table
but in a clearer, easier-to-use format. These revised LPD values reflect current light source efficiency data, recent research on light loss factors, and the latest IESNA light level
recommendations.
TABLE 9.3.1.2 Lighting Power Densities Using the Space-by-Space Method
| Common Space Types |
LPD (W/ft²) |
Building Specific Space Types (Continued) |
LPD (W/ft²) |
| Office-enclosed |
1.1 |
Fire Stations |
|
| Office-open plan |
1.1 |
Fire Station Engine room
|
0.8 |
| Conference/ Meeting/ Multipurpose |
1.3 |
Sleeping Quarters
|
0.3 |
| Classroom/ Lecture/ Training |
1.4 |
Post Office - Sorting Area |
1.2 |
|
For Penitentiary
|
1.3 |
Convention Center - Exhibit Space |
1.3 |
| Lobby |
1.3 |
Library |
|
|
For Hotel
|
1.1 |
Card File & Cataloguing
|
1.1 |
|
For Performing Arts Theater
|
3.3 |
Stacks
|
1.7 |
|
For Motion Picture Theatre
|
1.1 |
Reading Area
|
1.2 |
| Audience/ Seating Area |
0.9 |
Hospital |
|
|
For Gymnasium
|
0.4 |
Emergency
|
2.7 |
|
For Exercise Center
|
03. |
Recovery
|
0.8 |
|
For Convention Center
|
0.7 |
Nurse station
|
1.0 |
|
For Penitentiary
|
0.7 |
Exam/Treatment
|
1.5 |
|
For Religious Buildings
|
1.7 |
Pharmacy
|
1.2 |
|
For Sports Arena
|
0.4 |
Patient Room
|
0.7 |
|
For Performing Arts Theatre
|
2.6 |
Operating Room
|
2.2 |
|
For Motion Picture theatre
|
1.2 |
Nursery
|
0.6 |
|
For Transportation
|
0.5 |
Medical Supply
|
1.4 |
| Atrium-first three floors |
0.6 |
Physical Therapy
|
0.9 |
| Atrium-each additional floor |
0.2 |
Radiology
|
0.4 |
| Lounge/Recreation |
1.2 |
Laundry-Washing
|
0.6 |
|
For Hospital
|
0.8 |
Automotive – Service/Repair |
0.7 |
| Dining are |
0.9 |
Manufacturing |
|
|
For Penitentiary
|
1.3 |
Low Bay (<25 ft Floor to Ceiling Height)
|
1.2 |
|
For Hotel
|
1.3 |
High Bay (>25 ft Floor to Ceiling Height)
|
1.7 |
|
For Motel
|
1.2 |
Detailed Manufacturing
|
2.1 |
|
For Bar Lounge/Leisure Dining
|
1.4 |
Equipment room
|
1.2 |
|
For Family Dining
|
2.1 |
Control room
|
0.5 |
| Food Preparation |
1 |
Hotel/ Motel Guest Rooms |
1.1 |
| Laboratory |
1.4 |
Dormitory - Living Quarters |
1.1 |
| Restrooms |
0.9 |
Museum |
|
| Dressing/Locker/Fitting Room |
0.6 |
General Exhibition
|
1.0 |
| Corridor/Transition |
0.5 |
Restoration
|
1.7 |
|
For Hospital
|
1.0 |
Bank/Office - Banking Activity Area |
1.5 |
|
For Manufacturing Facility
|
0.5 |
Religious Buildings |
|
| Stairs – active |
0.6 |
Worship-pulpit, choir
|
2.4 |
| Active Storage |
0.8 |
Fellowship Hall
|
0.9 |
|
For Hospital
|
0.9 |
Retail [For accent lighting see 9.3.1.2.1.(c)] |
|
| Inactive storage |
0.3 |
Sales area
|
2.1 |
|
For Museum
|
0.8 |
Mall Concourse
|
1.7 |
| Electrical/ mechanical |
1.5 |
Sports Arena |
|
| Workshop |
1.9 |
Ring Sports Area
|
2.7 |
| |
|
Court Sports Area
|
2.3 |
| Building Specific Space Types |
|
Indoor Playing Field Area
|
1.4 |
| Gymnasium/ Exercise Center |
|
Warehouse |
|
|
Playing Area
|
1.4 |
Fine Material Storage
|
1.4 |
|
Exercise Area
|
0.9 |
Medium/Bulky Material Storage
|
0.9 |
| Courthouse/ Police Station/ Penitentiary |
|
Parking Garage - Garage Area |
0.2 |
|
Courtroom
|
1.9 |
Transportation |
|
|
Confinement Cells
|
0.9 |
Airport - Concourse
|
0.6 |
|
Judges Chambers
|
1.3 |
Air/Train/Bus - Baggage Area
|
1.0 |
| |
|
Terminal - Ticket counter
|
1.5 |
a In cases where both a common space type and a building specific space type are listed, the building specific space type shall apply.
TABLE 9.3.1.1
Lighting Power Densities
Using the Building Area Method
| Building Area Type |
Lighting Power Density (W/m²) |
| Automotive Facility |
10 |
| Convention Center |
13 |
| Court House |
13 |
| Dining: Bar Lounge/Leisure |
13 |
| Dining: Cafeteria/Fast Food |
15 |
| Dining: Family |
17 |
| Dormitory |
11 |
| Exercise Center |
11 |
| Gymnasium |
12 |
| Healthcare-Clinic |
11 |
| Hospital |
13 |
| Hotel |
11 |
| Library |
14 |
| Manufacturing Facility |
14 |
| Motel |
11 |
| Motion Picture Theatre |
13 |
| Multi-Family |
8 |
| Museum |
12 |
| Office |
11 |
| Parking Garage |
3 |
| Penitentiary |
11 |
| Performing Arts Theatre |
17 |
| Police/Fire Station |
11 |
| Post Office |
12 |
| Religious Building |
14 |
| Retail |
16 |
| School/University |
13 |
| Sports Arena |
12 |
| Town Hall |
12 |
| Transportation |
11 |
| Warehouse |
9 |
| Workshop |
15 |
a In cases where both general building area type and a specific building area type are listed, the specific building area type shall apply.
TABLE 9.3.1.2 Lighting Power Densities the Space by Space Method
| Space-by-Space Method Lighting Power Density(LPD) |
| Common Space Types |
LPD(W/m²) |
Building Specific Spaces Types (Continued) |
LPD(W/m²) |
| Office-enclosed |
1.1 |
Fire Stations |
|
| Office-open plan |
1.1 |
Fire Station Engine Room
|
0.8 |
| Conference-Meeting-Multipurpose |
1.3 |
Sleeping Quarters
|
0.3 |
| Classroom-Lecture-Training |
1.4 |
Post Office- Sorting Area |
1.2 |
|
For Penitentiary
|
1.3 |
Convention Center- Exhibit Space |
1.3 |
| Lobby |
1.3 |
Library |
|
|
For Hotel
|
1.1 |
Card File&Cataloguing
|
1.1 |
|
For Performing Arts Theater
|
3.3 |
Stacks
|
1.7 |
|
For Motion Picture Theater
|
1.1 |
Reading Area
|
1.2 |
| Audience-Seating Area |
0.9 |
Hospital |
|
|
For Gymnasium
|
0.4 |
Emergency
|
2.7 |
|
For Exercise Center
|
0.3 |
Recovery
|
0.8 |
|
For Covenanting Center
|
0.7 |
Nurse Station
|
1.0 |
|
For Penitentiary
|
0.7 |
Exam-Treatment
|
1.5 |
|
For Religious Buildings
|
1.7 |
Pharmacy
|
1.2 |
|
For Sports Arena
|
0.4 |
Patient Room
|
0.7 |
|
For Performing Arts Theatre
|
2.6 |
Operating Room
|
2.2 |
|
For Motion Picture Theatre
|
1.2 |
Nursery
|
0.6 |
|
For Transportation
|
0.5 |
Medical Supply
|
1.4 |
| Atrium-first three floors |
0.6 |
Physical Therapy
|
0.9 |
| Atrium-each additional floor |
0.2 |
Radiology
|
0.4 |
| Lounge-Recreation |
1.2 |
Laundry-Washing
|
0.6 |
|
For Hospital
|
0.8 |
Automotive-Service-Repair |
0.7 |
| Dining area |
0.9 |
Manufacturing |
|
|
For Penitentiary
|
1.3 |
Low Bay(<25 ft Floor to Ceiling Height)
|
1.2 |
|
For Hotel
|
1.3 |
High Bay(<25 ft Floor to Ceiling Height)
|
1.7 |
|
For Motel
|
1.2 |
Detailed Manufacturing
|
2.1 |
|
For Bar Lounge-Leisure Dining
|
1.4 |
Equipment Room
|
1.2 |
|
For Family Dining
|
2.1 |
Control Room
|
0.5 |
| Food Preparation |
1.2 |
Hotel-Motel Guest Rooms |
1.1 |
| Laboratory |
1.4 |
Dormitory-Living Quarters |
1.1 |
| Restrooms |
0.9 |
Museum |
|
| Dressing-Locker-Fitting Room |
0.6 |
General Exhibition
|
1.0 |
| Corridor-Transition |
0.5 |
Restoration
|
1.7 |
|
For Hospital
|
1.0 |
Bank-Office-Banking Activity Area |
1.5 |
|
For Manufacturing Facility
|
0.5 |
Religious Buildings |
|
| Stairs - active |
6 |
Worship-pulpit, choir
|
26 |
| Active Storage |
9 |
Fellowship Hall
|
10 |
|
For Hospital
|
10 |
Retail [For accent lighting see 9.3.1.2.1(c)] |
|
| Inactive storage |
3 |
Sales area
|
23 |
|
For Museum
|
9 |
Mall Concourse
|
18 |
| Electrical/ mechanical |
16 |
Sports Arena |
|
| Workshop |
20 |
Ring Sports Area
|
29 |
| |
|
Court Sports Area
|
25 |
| Building Specific Space Types |
|
Indoor Playing Field Area
|
15 |
| Gymnasium/ Exercise Center |
|
Warehouse |
|
|
Playing Area
|
15 |
Fine Material Storage
|
15 |
|
Exercise Area
|
10 |
Medium/Bulky Material Storage
|
10 |
| Courthouse/ Police Station/ Penitentiary |
|
Parking Garage - Garage Area |
2 |
|
Courtroom
|
20 |
Transportation |
|
|
Confinement Cells
|
10 |
Airport - Concourse
|
6 |
|
Judges Chambers
|
14 |
Air/Train/Bus - Baggage Area
|
11 |
| |
|
Terminal - Ticket counter
|
16 |
a In cases where both a common space type and a building specific space type are listed, the building specific space type shall apply.
11.4.5 Lighting. Lighting power in the budget building design shall be determined using the same categorization procedure (building area or space function) and
categories as the proposed design with lighting power set equal to the maxi-mum allowed for the corresponding method and category in 9.3. Power for fixtures not included in the lighting power
density calculation shall be modeled identically in the proposed and budget building. Lighting controls shall be the minimum required.
Addendum ae to 90.1-2001 (I-P and SI editions)
Revise Section 9.2.1.2 as follows:
9.2.1.2 Space Control. Each space enclosed by ceiling height partitions shall have at least one control device to independently control the general lighting within
the space. Each manual device shall be readily accessible and located so the occupants can see the controlled lighting.
- A control device shall be installed that automatically turns lighting off within 30 minutes of all occupants leaving a space, except spaces with multi-scene control,in:
- Classrooms (not including shop classrooms, laboratory classrooms, and preschool through 12th grade classrooms)
- Conference/meeting rooms
- Employee lunch and break rooms
These spaces are not required to be connected to other automatic lighting shutoff controls.
- For all other spaces, control device shall be activated either manually by an occupant or automatically by sensing an occupant. Each control device shall a. control a maximum of 2500 ft²
(232 m2) area for a space 10,000 ft² (929 m2) or less and a maximum of 10,000 ft² (929 m²) area for a space greater than 10,000 ft² (929 m²), and be capable of overriding
any time-of-day scheduled shutoff control for no more than four hours,
Exception to 9.2.1.2: Remote location shall be permitted for reasons of safety or security when the remote control device has an indicator pilot
light as part of or next to the control device and the light is clearly labeled to identify the controlled lighting.
TABLE 9.3.1.2 Lighting Power Densities Using the Space-by-Space Method
| Common Space Types |
LPD(W/ft²) |
Building Specific Space Types |
LPD (W/ft²) |
| Office-enclosed |
1.1 |
Gymnasium/ Exercise Center |
|
| Office-open plan |
1.1 |
Playing Area
|
1.4 |
| Conference/ Meeting/ Multipurpose |
1.3 |
Exercise Area
|
0.9 |
| Classroom/ Lecture/ Training |
1.4 |
Courthouse/ Police Station/ Penitentiary |
|
|
For Penitentiary
|
1.3 |
Courtroom
|
1.9 |
| Lobby |
1.3 |
Confinement Cells
|
0.9 |
|
For Hotel
|
1.1 |
Judges Chambers
|
1.3 |
|
For Performing Arts Theater
|
3.3 |
Fire Stations |
|
|
For Motion Picture Theatre
|
1.1 |
Fire Station Engine room
|
0.8 |
| Audience/ Seating Area |
0.9 |
Sleeping Quarters
|
0.3 |
|
For Gymnasium
|
0.4 |
Post Office—Sorting Area |
1.2 |
|
For Exercise Center
|
0.3 |
Convention Center—Exhibit Space |
1.3 |
|
For Convention Center
|
0.4 |
Library |
|
|
For Penitentiary
|
0.4 |
Card File & Cataloguing
|
1.1 |
|
For Religious Buildings
|
1.4 |
Stacks
|
1.7 |
|
For Sports Arena
|
0.4 |
Reading Area
|
1.2 |
|
For Performing Arts Theatre
|
2.6 |
Hospital |
|
|
For Motion Picture theatre
|
1.2 |
Emergency
|
2.7 |
|
For Transportation
|
0.5 |
Recovery
|
0.8 |
| Atrium-first three floors |
0.6 |
Nurse station
|
1.0 |
| Atrium-each additional floor |
0.2 |
Exam/Treatment
|
1.5 |
| Lounge/Recreation |
1.2 |
Pharmacy
|
1.2 |
|
For Hospital
|
0. |
Patient Room
|
0.7 |
| Dining area |
0.9 |
Operating Room
|
2.2 |
|
For Penitentiary
|
1.3 |
Nursery
|
0.6 |
|
For Hotel
|
1.3 |
Medical Supply
|
1.4 |
|
For Motel
|
1.2 |
Physical Therapy
|
0.9 |
|
For Bar Lounge/Leisure Dining
|
1.4 |
Radiology
|
0.4 |
|
For Family Dining
|
2.1 |
Laundry—Washing
|
0.6 |
| Food Preparation |
1.2 |
Automotive—Service/Repair |
0.7 |
| Laboratory |
1.4 |
Manufacturing |
|
| Restrooms |
0.9 |
Low Bay (<25 ft Floor to Ceiling Height)
|
1.2 |
| Dressing/Locker/Fitting Room |
0.6 |
High Bay (>25 ft Floor to Ceiling Height)
|
1.7 |
| Corridor/Transition |
0.5 |
Detailed Manufacturing
|
2.1 |
|
For Hospital
|
1.0 |
Equipment room
|
1.2 |
|
For Manufacturing Facility
|
0.5 |
Control room
|
0.5 |
| Stairs – active |
0.6 |
Hotel/ Motel Guest Rooms |
1.1 |
| Active Storage |
0.8 |
Dormitory—Living Quarters |
1.1 |
|
For Hospital
|
0.9 |
Museum |
|
| Inactive storage |
0.3 |
General Exhibition
|
1.0 |
|
For Museum
|
0.8 |
Restoration
|
1.7 |
| Electrical/ mechanical |
1.5 |
Bank/Office—Banking Activity Area |
1.5 |
| Workshop |
1.9 |
Religious Buildings |
|
| |
|
Worship-pulpit, choir
|
2.4 |
| |
|
Fellowship Hall
|
0.9 |
| |
|
Retail [For accent lighting see 9.3.1.2.1.(c)] |
|
| |
|
Sales area
|
1.7 |
| |
|
Mall Concourse
|
1.7 |
| |
|
Sports Arena |
|
| |
|
Ring Sports Area
|
2.7 |
| |
|
Court Sports Area
|
2.3 |
| |
|
Indoor Playing Field Area
|
1.4 |
| |
|
Warehouse |
|
| |
|
Fine Material Storage
|
1.4 |
| |
|
Medium/Bulky Material Storage
|
0.9 |
| |
|
Parking Garage—Garage Area |
0.2 |
| |
|
Transportation |
|
| |
|
Airport—Concourse
|
0.6 |
| |
|
Air/Train/Bus—Baggage Area
|
1.0 |
| |
|
Terminal—Ticket counter
|
1.5 |
a In cases where both a common space type and a building specific space type are listed, the building specific space type shall apply.
SI Version:
TABLE 9.3.1.2
Lighting Power Densities Using the Space-by-Space Method
| Common Space Types |
LPD (W/m2) |
Building Specific Space Types |
LPD (W/m2) |
| Office-enclosed |
12 |
Gymnasium/ Exercise Center |
|
| Office-open plan |
12 |
Playing Area
|
15 |
| Conference/ Meeting/ Multipurpose |
14 |
Exercise Area
|
10 |
| Classroom/ Lecture/ Training |
15 |
Courthouse/ Police Station/ Penitentiary |
20 |
|
For Penitentiary
|
14 |
Courtroom
|
10 |
| Lobby |
14 |
Confinement Cells
|
14 |
|
For Hotel
|
12 |
Judges Chambers
|
|
|
For Performing Arts Theater
|
36 |
Fire Stations |
9 |
|
For Motion Picture Theatre
|
12 |
Fire Station Engine room
|
3 |
| Audience/ Seating Area |
10 |
Sleeping Quarters
|
13 |
|
For Gymnasium
|
4 |
Post Office—Sorting Area |
14 |
|
For Exercise Center
|
3 |
Convention Center—Exhibit Space |
|
|
For Convention Center
|
8 |
Library |
9 |
|
For Penitentiary
|
8 |
Card File & Cataloguing
|
3 |
|
For Religious Buildings
|
18 |
Stacks
|
13 |
|
For Sports Arena
|
4 |
Reading Area
|
14 |
|
For Performing Arts Theatre
|
28 |
Hospital |
|
|
For Motion Picture theatre
|
13 |
Emergency
|
12 |
|
For Transportation
|
5 |
Recovery
|
18 |
| Atrium-first three floors |
6 |
Nurse station
|
13 |
| Atrium-each additional floor |
2 |
Exam/Treatment
|
|
| Lounge/Recreation |
13 |
Pharmacy
|
29 |
|
For Hospital
|
9 |
Patient Room
|
9 |
| Dining area |
10 |
Operating Room
|
11 |
|
For Penitentiary
|
14 |
Nursery
|
16 |
|
For Hotel
|
14 |
Medical Supply
|
13 |
|
For Motel
|
13 |
Physical Therapy
|
8 |
|
For Bar Lounge/Leisure Dining
|
15 |
Radiology
|
24 |
|
For Family Dining
|
23 |
Laundry—Washing
|
6 |
| Food Preparation |
13 |
Automotive—Service/Repair |
15 |
| Laboratory |
15 |
Manufacturing |
10 |
| Restrooms |
10 |
Low Bay (<25 ft Floor to Ceiling Height)
|
4 |
| Dressing/Locker/Fitting Room |
6 |
High Bay (>25 ft Floor to Ceiling Height)
|
6 |
| Corridor/Transition |
5 |
Detailed Manufacturing
|
23 |
|
For Hospital
|
11 |
Equipment room
|
13 |
|
For Manufacturing Facility
|
5 |
Control room
|
5 |
| Stairs—active |
6 |
Hotel/ Motel Guest Rooms |
12 |
| Active Storage |
9 |
Dormitory—Living Quarters |
12 |
|
For Hospital
|
10 |
Museum |
|
| Inactive storage |
3 |
General Exhibition
|
11 |
|
For Museum
|
9 |
Restoration
|
18 |
| Electrical/ mechanical |
16 |
Bank/Office—Banking Activity Area |
16 |
| Workshop |
20 |
Religious Buildings |
|
| |
|
Worship-pulpit, choir
|
26 |
| |
|
Fellowship Hall
|
10 |
| |
|
Retail [For accent lighting see 9.3.1.2.1.(c)] |
|
| |
|
Sales area
|
18 |
| |
|
Mall Concourse
|
18 |
| |
|
Sports Arena |
|
| |
|
Ring Sports Area
|
29 |
| |
|
Court Sports Area
|
25 |
| |
|
Indoor Playing Field Area
|
15 |
| |
|
Warehouse |
|
| |
|
Fine Material Storage
|
15 |
| |
|
Medium/Bulky Material Storage
|
10 |
| |
|
Parking Garage—Garage Area |
2 |
| |
|
Transportation |
|
| |
|
Airport—Concourse
|
6 |
| |
|
Air/Train/Bus—Baggage Area
|
11 |
| |
|
Terminal—Ticket counter
|
16 |
a In cases where both a common space type and a building specific space type are listed, the building specific space type shall apply.
INTERPRETATION IC 90.1-2001-5 OF
ANSI/ASHRAE/IESNA STANDARD 90.1-2001
Energy Standard for Buildings Except Low-Rise Residential Buildings
Revision Approved: April 22, 2002
Originally issued as interpretation of Standard 90.1-1999 on February 4, 2000 (IC 90.1-1999-1), but revised based on the publication of 90.1-2001. Revisions made to all Background, Question and
Answer statements to reflect Standard 90.1-2001 language.
Request from:Charles Eley, Eley Associates, 142 Minna Street, San Francisco, California 94105
Reference: This request for interpretation refers to the requirements presented in ANSI/ASHRAE/IESNA Standard 90.1-2001, Section 9.3.2, relating to the exterior lighting power
allowance.
Background: Section 9.3.2 has lighting power limits for exterior building lighting. Table 9.3.2 has limits for building entrances with a canopy, building entrances without a canopy, and
building exits. For a single building, the standard permits trade-offs between these three applications.
Interpretation: For multi-building projects, exterior lighting power can be traded off between buildings. Each building does not have to separately meet its exterior lighting power
allowance.
Question: Is this interpretation correct?
Answer: Yes. The exterior lighting power allowance of a multi-building project is the sum of lighting power allowances for the applicable exterior entrances (with and without canopies)
and exits of all buildings.
Comments: The designer is provided with additional flexibility for relatively minor lighting loads without changing the total amount of exterior power allowance for the total project.
Building facades are not part of the exterior lighting power allowance. Building facade lighting power is “use-it or lose-it”.
ASHRAE 90.1 - 2007
3. DEFINITIONS, ABBREVIATIONS, AND ACRONYMS
…
fenestration:all areas (including the frames) in the building envelope that let in light, including windows, plastic panels, clerestories, skylights, glass doors that are more than
one-half glass, and glass block walls. (See building envelope and door.)
(a) skylight: a fenestration surface having a slope of less than 60 degrees from the horizontal plane. Other fenestration, even if mounted on the roof of a building, is considered
vertical fenestration.
(b) vertical fenestration: all fenestration other than skylights. Trombe wall assemblies, where glazing is installed within 12 in. of a mass wall, are considered walls, not
fenestration.
fenestration area: total area of the fenestration measured using the rough opening and including the glazing, sash, and frame. For doors where the glazed vision area is less than
50% of the door area, the fenestration area is the glazed vision area. For all other doors, the fenestration area is the door area. (See door area.)
fenestration, vertical: (See fenestration and skylight.)
…
lighting power allowance:
(a)interior lighting power allowance: the maximum lighting power in watts allowed for the interior of a building.
(b)exterior lighting power allowance: the maximum lighting power in watts allowed for the exterior of a building.
lighting power density (LPD): the maximum lighting power per unit area of a building classification of space function.
…
occupant sensor: a device that detects the presence or absence of people within an area and causes lighting, equipment, or appliances to be regulated accordingly.
…
4. ADMINISTRATION AND ENFORCEMENT
…
4.1.1.4 Replacement of Portions of Existing Buildings: Portions of a building envelope, heating, ventilating, air-conditioning, service water heating, power, lighting, and other systems
and equipment that are being replaced shall be considered as Alterations of Existing Buildings and shall comply with the Standard as described in Section 4.2.
4.1.1.5 Changes in Space Conditioning. Whenever unconditioned or semiheated spaces in a building are converted to conditioned spaces, such conditioned spaces
shall be brought into compliance with all the applicable requirements of this standard that would apply to the building envelope, heating, ventilating, air-conditioning, service water heating,
power, lighting, and other systems and equipment of the space as if the building were new.
…
4.2 Compliance
4.2.1 Compliance Paths
4.2.1.1 New Buildings: New Buildings shall comply with either the provisions of Sections 5, 6, 7, 8, 9, and 10 or Section 11.
4.2.1.2 Additions to Existing Buildings: Additions to existing buildings shall comply with either the provisions of Sections 5, 6, 7, 8, 9, and 10 or Section 11.
Exception to 4.2.1.2: When an addition to an existing building cannot comply by itself, trade-offs will be allowed by modification to one or more of the existing components of the
existing building. Modeling of the modified components of the existing building and addition shall employ the procedures of Section 11; and the addition shall not increase the
energy consumption of the existing building plus the addition beyond the energy that would be consumed by the existing building plus the addition if the addition alone did comply.
4.2.1.3 Alterations of Existing Buildings: Alterations of existing buildings shall comply with the provisions of Sections 5, 6, 7, 8, 9, and 10, provided, however that
nothing in this standard shall require compliance with any provision of this standard if such compliance will result in the increase of energy consumption of the building.
Exceptions to 4.2.1.3:
(a) A building that has been specifically designated as historically significant by the adopting authority or is listed in “The National Register of Historic Places” or has
been determined to be eligible for listing by the U.S Secretary of the Interior need not comply with these requirements.
(b) Where one or more components of an existing building or portions thereof are being replaced, the annual energy consumption of the comprehensive design shall not be greater
than the annual energy consumption of a substantially identical design, using the same energy types, in which the applicable requirements of Sections 5, 6, 7, 8, 9, and 10, as provided in
4.2.1.3, and such compliance is verified by a design professional, by the use of any calculation methods acceptable to the authority having jurisdiction.
…
5.8.1.6 Recessed Equipment. Lighting fixtures; heating, ventilating, and air-conditioning equipment, including wall heaters, ducts, and plenums; and other equipment shall not be recessed
in such a manner as to affect the insulation thickness unless:
(a) the total combined area affected (including necessary clearances) is less than one percent of the opaque area of the assembly, or
(b) the entire roof, wall, or floor is covered with insulation to the full depth required, or
(c) the effects of reduced insulation are included in calculations using an area-weighted average method and compressed insulation values obtained from Table A9.4.C. In all cases, air leakage
through or around the recessed equipment to the conditioned space shall be limited in accordance with 5.4.3.
…
9. LIGHTING
9.1 General
9.1.1 Scope: This section shall apply to the following:
(a) interior spaces of buildings;
(b) exterior building features, including facades, illuminated roofs, architectural features, entrances, exits, loading docks, and illuminated canopies; and
(c) exterior building grounds lighting provided through the building's electrical service.
Exceptions to 9.1.1:
(a) emergency lighting that is automatically off during normal building operation,
(b) lighting within living units,
(c) lighting that is specifically designated as required by a health or life safety statute, ordinance, or regulation,
(d) decorative gas lighting systems.
9.1.2 Lighting Alterations. The replacement of lighting systems in any building space shall comply with the lighting power density requirements of Section 9 applicable to that
space. New lighting systems shall comply with the applicable lighting power density requirements of Section 9. Any new control devices as a direct replacement of existing control
devices shall comply with the specific requirements of 9.4.1.2(b).
Exception to 9.1.2: Alterations that replace less than 50% of the luminaires in a space need not comply with these requirements provided that such alterations
do not increase the installed interior lighting power.
9.1.3 Installed Interior Lighting Power. The installed interior lighting power shall include all power used by the luminaires, including lamps, ballasts,
current regulators, and control devices except as specifically exempted in 9.2.2.3.
Exception to 9.1.3: If two or more independently operating lighting systems in a space are capable of being controlled to prevent simultaneous user operation, the installed interior
lighting power shall be based solely on the lighting system with the highest wattage.
9.1.4 Luminaire Wattage. Luminaire wattage incorporated into the installed interior lighting power shall be determined in accordance with the following criteria:
(a) The wattage of incandescent or tungsten-halogen luminaires with medium screw base sockets and not containing permanently installed ballasts shall be the maximum labeled wattage of the
luminaire.
(b) The wattage of luminaires with permanently installed or remote ballasts or transformers shall be the operating input wattage of the maximum lamp/ auxiliary combination based on values
from the auxiliary manufacturer’s literature or recognized testing laboratories.
(c) The wattage of line-voltage lighting track and plug-in busway that allow the addition and/or relocation of luminaires without altering the wiring of the system shall be the specified wattage
of the luminaires included in the system with a minimum of 30 W/lin ft.
(d) The wattage of low-voltage lighting track, cable conductor, rail conductor, and other flexible lighting systems that allow the addition and/or relocation of luminaires without altering the
wiring of the system shall be the specified wattage of the transformer supplying the system.
(e) The wattage of all other miscellaneous lighting equipment shall be the specified wattage of the lighting equipment.
9.2 Compliance Path(s)
9.2.1 Lighting systems and equipment shall comply with 9.1, General; 9.4, Mandatory Provisions; and the prescriptive requirements of either:
(a) 9.5, Building Area Method, or
(b) 9.6, Space-by-Space Method.
9.2.2 Prescriptive Requirements
9.2.2.1 The Building Area Method for determining the interior lighting power allowance, described in 9.5, is a simplified approach for demonstrating compliance.
9.2.2.2 The Space-by-Space Method, described in 9.6, is an alternative approach that allows greater flexibility.
9.2.2.3 Interior Lighting Power. The interior lighting power allowance for a building or a separately metered or permitted portion of a building shall be determined by
either the Building Area Method described in 9.5 or the Space-by-Space Method described in 9.6. Trade-offs of interior lighting power allowance among portions of the building
for which a different method of calculation has been used are not permitted. The installed interior lighting power identified in accordance with 9.1.3 shall not exceed the interior
lighting power allowance developed in accordance with 9.5 or 9.6.
Exceptions to 9.2.2.3: The following lighting equipment and applications shall not be considered when determining the interior lighting power allowance developed in
accordance with 9.5 or 9.6, nor shall the wattage for such lighting be included in the installed interior lighting power identified in accordance with 9.1.3. However, any such lighting
shall not be exempt unless it is an addition to general lighting and is controlled by an independent control device.
(a) Display or accent lighting that is an essential element for the function performed in galleries, museums, and monuments.
(b) Lighting that is integral to equipment or instrumentation and is installed by its manufacturer.
(c) Lighting specifically designed for use only during medical or dental procedures and lighting integral to medical equipment.
(d) Lighting integral to both open and glass-enclosed refrigerator and freezer cases.
(e) Lighting integral to food warming and food preparation equipment.
(f) Lighting for plant growth or maintenance.
(g) Lighting in spaces specifically designed for use by the visually impaired.
(h) Lighting in retail display windows, provided the display area is enclosed by ceiling-height partitions.
(i) Lighting in interior spaces that have been specifically designated as a registered interior historic landmark.
(j) Lighting that is an integral part of advertising or directional signage.
(k) Exit signs.
(l) Lighting that is for sale or lighting educational demonstration systems.
(m) Lighting for theatrical purposes, including performance, stage, and film and video production.
(n) Lighting for television broadcasting in sporting activity areas.
(o) Casino gaming areas.
…
9.4 Mandatory Provisions
9.4.1 Lighting Control
9.4.1.1 Automatic Lighting Shutoff. Interior lighting in buildings larger than 5000 ft² shall be controlled with an automatic control device to shut off building
lighting in all spaces. This automatic control device shall function on either
(a) a scheduled basis using a time-of-day operated control device that turns lighting off at specific programmed times—an independent program schedule shall be provided for areas of no more
than 25,000 ft² but not more than one floor—or
(b) an occupant sensor that shall turn lighting off within 30 minutes of an occupant leaving a space—or
(c) a signal from another control or alarm system that indicates the area is unoccupied.
Exceptions to 9.4.1.1: The following shall not require an automatic control device:
(a) Lighting intended for 24-hour operation
(b) Lighting in spaces where patient care is rendered.
(c) Spaces where an automatic shutoff would endanger the safety or security of the room or building occupant(s).
9.4.1.2 Space Control. Each space enclosed by ceiling-height partitions shall have at least one control device to independently control the general lighting within the
space. Each manual device shall be readily accessible and located so the occupants can see the controlled lighting.
(a) A control device shall be installed that automatically turns lighting off within 30 minutes of all occupants leaving a space, except spaces with multi-scene control, in
- classrooms (not including shop classrooms, laboratory classrooms, and preschool through 12th grade classrooms),
- conference/meeting rooms,
- employee lunch and break rooms.
These spaces are not required to be connected to other automatic lighting shutoff controls.
(b) For all other spaces, each control device shall be activated either manually by an occupant or automatically by sensing an occupant. Each control device shall control a
maximum of 2500 ft² area for a space 10,000 ft² or less and a maximum of 10,000 ft² area for a space greater than 10,000 ft2 and be capable of overriding any time-of-day
scheduled shutoff control for no more than four hours.
Exception to 9.4.1.2: Remote location shall be permitted for reasons of safety or security when the remote control device has an indicator pilot light as part of or next to the control
device and the light is clearly labeled to identify the controlled lighting.
9.4.1.3 Exterior Lighting Control. Lighting for all exterior applications not exempted in 9.1 shall have automatic controls capable of turning off exterior lighting when sufficient
daylight is available or when the lighting is not required during nighttime hours. Lighting not designated for dusk-todawn operation shall be controlled by an astronomical time switch. Lighting
designated for dusk-to-dawn operation shall be controlled by an astronomical time switch or photosensor. Astronomical time switches shall be capable of retaining programming and the time setting
during loss of power for a period of at least 10 hours.
Exception to 9.4.1.3: Lighting for covered vehicle entrances or exits from buildings or parking structures where required for safety, security, or eye adaptation.
9.4.1.4 Additional Control.
(a) Display/Accent Lighting—display or accent lighting shall have a separate control device.
(b) Case Lighting—lighting in cases used for display purposes shall have a separate control device.
(c) Hotel and Motel Guest Room Lighting—hotel and motel guest rooms and guest suites shall have a master control device at the main room entry that controls all
permanently installed luminaires and switched receptacles.
(d) Task Lighting—supplemental task lighting, including permanently installed undershelf or undercabinet lighting, shall have a control device integral to the
luminaires or be controlled by a wall-mounted control device provided the control device is readily accessible and located so that the occupant can see the controlled
lighting.
(e) Nonvisual Lighting—lighting for nonvisual applications, such as plant growth and food warming, shall have a separate control device.
(f) Demonstration Lighting—lighting equipment that is for sale or for demonstrations in lighting education shall have a separate control device.
9.4.2 Tandem Wiring. Luminaires designed for use with one or three linear fluorescent lamps greater than 30 W each shall use two-lamp tandem-wired ballasts in place of single-lamp ballasts
when two or more luminaires are in the same space and on the same control device.
Exceptions to 9.4.2:
(a) Recessed luminaires more than 10 ft apart measured center to center.
(b) Surface-mounted or pendant luminaires that are not continuous.
(c) Luminaires using single-lamp high-frequency electronic ballasts.
(d) Luminaires using three-lamp high-frequency electronic or three-lamp electromagnetic ballasts.
(e) Luminaires on emergency circuits.
(f) Luminaires with no available pair.
(d) Luminaires using three-lamp high-frequency electronic or three-lamp electromagnetic ballasts.
(e) Luminaires on emergency circuits.
(f) Luminaires with no available pair.
9.4.3 Exit Signs. Internally illuminated exit signs shall not exceed 5 watts per face.
9.4.4 Exterior Building Grounds Lighting. All exterior building grounds luminaires that operate at greater than 100 watts shall contain lamps having a minimum efficacy of 60 lm/W unless
the luminaire is controlled by a motion sensor or qualifies for one of the exceptions under 9.1.1 or 9.4.5.
9.4.5 Exterior Building Lighting Power. The total exterior lighting power allowance for all exterior building applications is the sum of the individual lighting power densities permitted
in Table 9.4.5 for these applications plus an additional unrestricted allowance of 5% of that sum. Trade-offs are allowed only among exterior lighting applications listed in the Table 9.4.5
“Tradable Surfaces” section.
Exceptions to 9.4.5: Lighting used for the following exterior applications is exempt when equipped with a control device independent of the control of the nonexempt lighting:
(a) Specialized signal, directional, and marker lighting associated with transportation.
(b) Advertising signage or directional signage.
(c) Lighting integral to equipment or instrumentation and installed by its manufacturer.
(d) Lighting for theatrical purposes, including performance, stage, film production, and video production.
(e) Lighting for athletic playing areas.
(f) Temporary lighting.
(g) Lighting for industrial production, material handling, transportation sites, and associated storage areas.
(h) Theme elements in theme/amusement parks.
(i) Lighting used to highlight features of public monuments and registered historic landmark structures or buildings.
9.5 Building Area Method Compliance Path
9.5.1 Building Area Method of Calculating Interior Lighting Power Allowance. Use the following steps to determine the interior lighting power allowance by the building area method:
(a) Determine the appropriate building area type from Table 9.5.1 and the allowed lighting power density (watts per unit area) from the building area method column. For building area types not
listed, selection of a reasonably equivalent type shall be permitted.
(b) Determine the gross lighted floor area (square feet) of the building area type.
(c) Multiply the gross lighted floor areas of the building area type(s) times the lighting power density.
(d) The interior lighting power allowance for the building is the sum of the lighting power allowances of all building area types. Trade-offs among building area types are permitted provided that
the total installed interior lighting power does not exceed the interior lighting power allowance.
9.6 Alternative Compliance Path: Space-by-Space Method
9.6.1 Space-by-Space Method of Calculating Interior Lighting Power Allowance. Use the following steps to determine the interior lighting power allowance by the space-byspace method:
(a) Determine the appropriate building type from Table 9.6.1. For building types not listed, selection of a reasonably equivalent type shall be permitted.
(b) For each space enclosed by partitions 80% or greater than ceiling height, determine the gross interior floor area by measuring to the center of the partition wall. Include the floor area of
balconies or other projections. Retail spaces do not have to comply with the 80% partition heightrequirements.
(c) Determine the interior lighting power allowance by using the columns designated space-by-space method in Table 9.6.1. Multiply the floor area(s) of the space(s) times the allowed lighting
power density for the space type that most closely represents the proposed use of the space(s). The product is the lighting power allowance for the space(s). For space types not listed,
selection of a reasonable equivalent category shall be permitted.
(d) The interior lighting power allowance is the sum of lighting power allowances of all spaces. Trade-offs among spaces are permitted provided that the total installed interior lighting power
does not exceed the interior lighting power allowance.
9.6.2 Additional Interior Lighting Power. When using the space-by-space method, an increase in the interior lighting power allowance is allowed for specific lighting functions.
Additional power shall be allowed only if the specified lighting is installed, shall be used only for the specified luminaires, and shall not be used for any other purpose or in any other
space.
9.6.3 An increase in the interior lighting power allowance is permitted in the following cases:
(a) For spaces in which lighting is specified to be installed in addition to the general lighting for the purpose of decorative appearance, such as chandelier-type luminaries or sconces or for
highlighting art or exhibits, provided that the additional lighting power shall not exceed 1.0 W/ft2 of such spaces.
(b) For spaces in which lighting is specified to be installed to meet the requirements of visual display terminals as the primary viewing task, provided that the additional lighting power shall
not exceed 0.35 W/ft2 of such spaces and that the specified luminaire meets requirements for use in such spaces. Maximum average luminance measured from the vertical in candelas per square foot
of not more than 80 cd/ft2 at 65 degrees, 33 cd/ft2 at 75 degrees, and 17 cd/ft2 at 85 to 90 degrees.
(c) For lighting equipment installed in retail spaces that is specifically designed and directed to highlight merchandise, provided that the additional lighting power shall not exceed (1) 1.6
W/ft2 times the area of specific display or (2) 3.9 W/ft2 times the area of specific display for valuable merchandise, such as jewelry, fine apparel and accessories, china and silver, art, and
similar items, where detailed display and examination of merchandise are important.
TABLE 9.4.5 Lighting Power Densities for Building Exteriors
| Tradable Surfaces (Lighting power densities for uncovered parking areas, building grounds, building entrances and exits, canopies and overhangs and outdoor sales
areas may be traded.) |
| Uncovered Parking Areas |
| Parking Lots and drives |
0.15 W/ft² |
| Building Grounds |
| Walkways less than 10 feet wide |
1.0 W/linear foot |
|
Walkways 10 feet wide or greater
Plaza areas
Special Feature Areas
|
0.2 W/ft² |
| Stairways |
1.0 W/ft² |
| Building Entrances and Exits |
| Main entries |
30 W/linear foot of door width |
| Other doors |
20 W/linear foot of door width |
| Canopies and Overhangs |
| Canopies (free standing and attached and overhangs) |
1.25 W/ft² |
| Outdoor Sales |
| Open areas (including vehicle sales lots) |
0.5 W/ft² |
| Street frontage for vehicle sales lots in addition to “open area” allowance |
20 W/linear foot |
|
| Non-Tradable Surfaces (Lighting power density calculations for the following applications can be used only for the specific application and can-not be traded between surfaces or
with other exterior lighting. The following allowances are in addition to any allowance otherwise permitted in the “tradable Surfaces” section of this table.) |
| Building Facades |
0.2 W/ft² for each illuminated wall or surface or 5.0 W/linear foot for each illuminated wall or surface length |
| Automated teller machines and night depositories |
270 W per location plus 90 W per additional ATM per location |
| Entrances and gatehouse inspection stations at guarded facilities |
1.25 W/ft² of uncovered area (covered areas are included in the “Canopies and Overhangs” section of “Tradable Surfaces”) |
| Loading areas for law enforcement, fire, ambulance and other emergency service vehicles |
0.5 W/ft² of uncovered area (covered areas are included in the “Canopies and Overhangs” section of “Tradable Surfaces”) |
| Drive-up windows at fast food restaurants |
400 W per drive-through |
| Parking near 24-hour retail entrances |
800 W per main entry |
|
TABLE 9.5.1 Lighting Power Densities Using the Building Area Method
| Lighting Power Density |
| Building Area Typea |
(W/ft²) |
| Automotive Facility |
0.9 |
| Convention Center |
1.2 |
| Court House |
1.2 |
| Dining: Bar Lounge/Leisure |
1.3 |
| Dining: Cafeteria/Fast Food |
1.4 |
| Dining: Family |
1.6 |
| Dormitory |
1.0 |
| Exercise Center |
1.0 |
| Gymnasium |
1.1 |
| Health Care-Clinic |
1.0 |
| Hospital |
1.2 |
| Hotel |
1.0 |
| Library |
1.3 |
| Manufacturing Facility |
1.3 |
| Motel |
1.0 |
| Motion Picture Theater |
1.2 |
| Multi-Family |
0.7 |
| Museum |
1.1 |
| Office |
1.0 |
| Parking Garage |
0.3 |
| Penitentiary |
1.0 |
| Performing Arts Theater |
1.6 |
| Police/Fire Station |
1.0 |
| Post Office |
1.1 |
| Religious Building |
1.3 |
| Retail |
1.5 |
| School/University |
1.2 |
| Sports Arena |
1.1 |
| Town Hall |
1.1 |
| Transportation |
1.0 |
| Warehouse |
0.8 |
| Workshop |
1.4 |
| a In cases where both general building area type and a specific building area type are listed, the specific building area type shall apply. |
TABLE 9.6.1 Lighting Power Densities Using the Space-by-Space Method
| Common Space Typesa |
LPD (W/ft²) |
Building Specific Space Types |
LPD (W/ft²) |
| Office-Enclosed |
1.1 |
Gymnasium/Exercise Center |
|
| Office-Open Plan |
1.1 |
Playing Area |
1.4 |
| Conference/Meeting/Multipurpose |
1.3 |
Exercise Area |
0.9 |
| Classroom/Lecture/Training |
1.4 |
Courthouse/Police Station/Penitentiary |
|
| For Penitentiary |
1.3 |
Courtroom |
1.9 |
| Lobby |
1.3 |
Confinement Cells |
0.9 |
| For Hotel |
1.1 |
Judges Chambers |
1.3 |
| For Performing Arts Theater |
3.3 |
Fire Stations |
|
| For Motion Picture Theater |
1.1 |
Fire Station Engine Room |
0.8 |
| Audience/Seating Area |
0.9 |
Sleeping Quarters |
0.3 |
| For Gymnasium |
0.4 |
Post Office—Sorting Area |
1.2 |
| For Exercise Center |
0.3 |
Convention Center—Exhibit Space |
1.3 |
| For Convention Center |
0.7 |
Library |
|
| For Penitentiary |
0.7 |
Card File and Cataloging |
1.1 |
| For Religious Buildings |
1.7 |
Stacks |
1.7 |
| For Sports Arena |
0.4 |
Reading Area |
1.2 |
| For Performing Arts Theater |
2.6 |
Hospital |
|
| For Motion Picture Theater |
1.2 |
Emergency |
2.7 |
| For Transportation |
0.5 |
Recovery |
0.8 |
| Atrium—First Three Floors |
0.6 |
Nurse Station |
1.0 |
| Atrium—Each Additional Floor |
0.2 |
Exam/Treatment |
1.5 |
| Lounge/Recreation |
1.2 |
Pharmacy |
1.2 |
| For Hospital |
0.8 |
Patient Room |
0.7 |
| Dining Area |
0.9 |
Operating Room |
2.2 |
| For Penitentiary |
1.3 |
Nursery |
0.6 |
| For Hotel |
1.3 |
Medical Supply |
1.4 |
| For Motel |
1.2 |
Physical Therapy |
0.9 |
| For Bar Lounge/Leisure Dining |
1.4 |
Radiology |
0.4 |
| For Family Dining |
2.1 |
Laundry—Washing |
0.6 |
| Food Preparation |
1.2 |
Automotive—Service/Repair |
0.7 |
| Laboratory |
1.4 |
Manufacturing |
|
| Restrooms |
0.9 |
Low Bay (<25 ft Floor to Ceiling Height) |
1.2 |
| Dressing/Locker/Fitting Room |
0.6 |
High Bay (≥25 ft Floor to Ceiling Height) |
1.7 |
| Corridor/Transition |
0.5 |
Detailed Manufacturing |
2.1 |
| For Hospital |
1.0 |
Equipment Room |
1.2 |
| For Manufacturing Facility |
0.5 |
Control Room |
0.5 |
| Stairs—Active |
0.6 |
Hotel/Motel Guest Rooms |
1.1 |
| Active Storage |
0.8 |
Dormitory—Living Quarters |
1.1 |
| For Hospital |
0.9 |
Museum |
|
| Inactive storage |
0.3 |
General Exhibition |
1.0 |
| For Museum |
0.8 |
Restoration |
1.7 |
| Electrical/Mechanical |
1.5 |
Bank/Office—Banking Activity Area |
1.5 |
| Workshop |
1.9 |
Religious Buildings |
|
| |
|
Worship Pulpit, Choir |
2.4 |
| |
|
Fellowship Hall |
0.9 |
| |
|
Retail [For accent lighting, see 9.3.1.2.1(c)] |
|
| |
|
Sales Area |
1.7 |
| |
|
Mall Concourse |
1.7 |
| |
|
Sports Arena |
|
| |
|
Ring Sports Area |
2.7 |
| |
|
Court Sports Area |
2.3 |
| |
|
Indoor Playing Field Area |
1.4 |
| |
|
Warehouse |
|
| |
|
Fine Material Storage |
1.4 |
| |
|
Medium/Bulky Material Storage |
0.9 |
| |
|
Parking Garage—Garage Area |
0.2 |
| |
|
Transportation |
|
| |
|
Airport—Concourse |
0.6 |
| |
|
Air/Train/Bus—Baggage Area |
1.0 |
| |
|
Terminal—Ticket Counter |
1.5 |
a In cases where both a common space type and a building specific type are listed, the building specific space type shall apply.
ASHRAE 90.1 - 2007
4. ADMINSTRATION AND ENFORCEMENT
4.1 General
4.1.1.1 New Buildings. New buildings shall comply with the standard as described in Section 4.2.
4.1.1.2 Additions to Existing Buildings. An extension or increase in the floor area or height of a building outside of the existing
building envelope shall be considered additions to existing buildings and shall comply with the standard as described in Section 4.2.
4.1.1.3 Alterations of Existing Buildings. Alterations of existing buildings shall comply with the standard as described
in Section 4.2.
4.1.1.4 Replacement of Portions of Existing Buildings. Portions of a building envelope, heating, ventilating, air-conditioning, service
water heating, power, lighting, and other systems and equipment that are being replaced shall be considered as alterations of existing buildings and shall comply with the standard as described in
Section 4.2.
4.1.1.5 Changes in Space Conditioning. Whenever unconditioned or semiheated spaces in a building are converted to
conditioned spaces, such conditioned spaces shall be brought into compliance with all the applicable requirements of this standard that would apply to the building envelope,
heating, ventilating, air-conditioning, service water heating, power, lighting, and other systems and equipment of the space as if the building were new.
4.1.2 Administrative Requirements. Administrative requirements relating to permit requirements , enforcement by the authority having
jurisdiction, locally adopted energy standards, interpretations, claims of exemption, and rights of appeal are specified by the authority having jurisdiction.
4.1.3 Alternative Materials, Methods of Construction, or Design. The provisions of this standard are not intended to prevent the use of any
material, method of construction, design, equipment, or building system not specifically prescribed herein.
4.1.4 Validity. If any term, part, provision, section, paragraph, subdivision, table, chart, or referenced standard of this standard shall
be held unconstitutional, invalid, or ineffective, in whole or in part, such determination shall not be deemed to invalidate any remaining term, part, provision, section, paragraph, subdivision,
table, chart, or referenced standard of this standard.
4.1.5 Other Laws. The provisions of this standard shall not be deemed to nullify any provisions of local, state, or federal law. Where
there is a conflict between a requirement of this standard and such other law affecting construction of the building, precedence shall be determined by the authority having
jurisdiction.
4.1.6 Referenced Standards. The standards referenced in this standard and listed in Section 12 shall be considered part of the requirements
of this standard to the prescribed extent of such reference. Where differences occur between the provision of this standard and referenced standards, the provision of this standard shall apply.
Informative references are cited to acknowledge sources and are not part of this standard. They are identified in Informative Appendix E.
4.1.7 Normative Appendices. The normative appendices to this standard are considered to be integral parts of the mandatory requirements of
this standard, which, for reasons of convenience, are placed apart from all other normative elements.
4.1.8 Informative Appendices. The informative appendices to this standard and informative notes located within this standard contain
additional information and are not mandatory or part of this standard.
4.2 Compliance
4.2.1 Compliance Paths
4.2.1.1 New Buildings. New Buildings shall comply with either the provisions of Sections 5, 6, 7, 8, 9, and 10 or Section 11.
4.2.1.2 Additions to Existing Buildings. Additions to existing buildings shall comply with either the provisions of
Sections 5, 6, 7, 8, 9, and 10 or Sections 11.
Exceptions: When an addition to an existing building cannot comply by itself, trade-offs will be allowed by modification to one or
more of existing components of the existing building. Modeling of the modified components of the existing building and addition shall employ the procedures of Section 11; the
addition shall not increase the energy consumption of existing building plus the addition beyond the energy that would be consumed by the existing building plus the addition if the
addition alone did comply.
4.2.1.3 Alterations of Existing Buildings. Alterations of existing buildings shall comply with the provisions of Sections
5, 6, 7, 8, 9, and 10, provided, however, that nothing in this standard shall require compliance with any provision of this standard if such compliance will result in the increase of energy
consumption of the building.
Exceptions:
- A building that has been specifically designated as historically significant by the adopting authority or is listed in The National Register of Historic Places or has been determined
to be eligible for listing by the US Secretary of the Interior need not comply with these requirements.
- Where one or more components of an existing building or portions thereof are being replaced, the annual energy consumption of the comprehensive design shall not be greater than the
annual energy consumption of a substantially identical design, using the same energy types, in which the applicable requirements of Sections 5, 6, 7, 8, 9, and 10, as provided in Section 4.2.1.3,
and such compliance is verified by a design professional, by the use of any calculation methods acceptable to the authority having jurisdiction.
4.2.2 Compliance Documentation
4.2.2.1 Construction Details. Compliance documents shall show all the pertinent data and features of the building. equipment, and systems
in sufficient detail to permit a determination of compliance by building official and to indicate compliance with the requirements of this standard.
4.2.2.2 Supplemental Information. Supplemental information necessary to verify compliance with this standard, such as calculations,
worksheets, compliance forms, vendor literature, or other data, shall be made available when required by the building official.
4.2.2.3 Manuals. Operating and maintenance information shall be provided to the building owner. This information shall include, but not be
limited to, the information specified in Sections 6.7.2.2 and 8.7.2.
4.2.3 Labeling of Material and Equipment. Materials and equipment shall be labeled in a manner that will allow for a determination of their
compliance with the applicable provisions of this standard.
4.2.4 Inspections. All building construction, additions, or alterations subject to the provisions of this standard shall be
subject to inspection by the building official, and all such work shall remain accessible and exposed for inspection purposes until approved in accordance with the procedures specified by
the building official. Items for inspection include at least the following:
- wall insulation after the insulation and vapor retarder are in place but before concealment
- roof/ceiling insulation after roof/insulation is in place but before concealment
- slab/foundation wall after slab/foundation insulation is in place but before concealment
- fenestration after all glazing materials are in place
- mechanical systems and equipment and insulation after installation but before concealment
- electrical equipment and systems after installation but before concealment
5.8.1.6 Recessed Equipment. Lighting fixtures; heating, ventilating, and air-conditioning equipment, including wall heaters, ducts, and plenums;
and other equipment shall not be recessed in such a manner as to affect the insulation thickness unless
- the total combined area affected (including necessary clearances) is less than 1% of the opaque are of the assembly,
- the entire roof, wall, or floor is covered with insulation to the full depth required, or
- the effects of reduced insulation are included in calculations using an area-weighted average method and compressed insulation values obtained from Table A9.4.C.
In all cases, air leakage through or around the recessed equipment to the conditioned space shall be limited in accordance with Section 5.4.3.
9. LIGHTING
↓
|
9.2 – Definition of Compliance Paths
|
↓
|
9.4 – Mandatory Provisions
|
↓
| 9.6 – Space-by- Space Method |
|
| 9.5 – Building Area Method |
|
| Section 11 – Energy Cost Budget Method |
|
9.1 General
9.1.1 Scope. This section shall apply to the following:
- interior spaces of buildings
- exterior building features, including facades, illuminated roofs, architectural features, entrances, exists, loading docks, and illuminated canopies
- exterior building grounds lighting provided through the building’s electrical service
Exceptions:
- emergency lighting that is automatically off during normal building operation
- lighting within dwelling units
- lighting that is specifically designated as required by a health or life safety statute, ordinance, or regulation
- decorative gas lighting systems
9.1.2 Lighting Alterations. The replacement of lighting systems in any building space shall comply with the LPD requirements of Section 9
applicable to that space. New lighting systems shall comply with the applicable LPD requirements of Section 9. Any new control devices as a direct replacement of existing control
devices shall comply with the specific requirements of Section 9.4.1.2(b).
Exception: Alterations that replace less than 50% of the luminaires in a space need not comply with these requirements
provided that such alterations do not increase the installed interior lighting power.
9.1.3 Installed Interior Lighting Power. The installed interior lighting power shall include all power used by the luminaires,
including lamps, ballasts, transformers, and control devices except as specifically exempted in Section 9.2.2.3.
Exception: If two or more independently operating lighting systems in a space are capable of being controlled to prevent simultaneous user
operation, the installed interior lighting power shall be based solely on the lighting system with the highest wattage.
9.1.4 Luminaire Wattage. Luminaire wattage incorporated into the installed interior lighting power shall be determined in accordance with the
following criteria:
- The wattage of incandescent or tungsten-halogen luminaires with medium screw base sockets and not containing permanently installed ballasts shall be the maximum labeled wattage of the
luminaire.
- The wattage of luminaires with permanently installed or remote ballasts or transformers shall be the operating input wattage of the maximum lamp/auxiliary combination based on values
from the auxiliary manufacturers’ literature or recognized testing laboratories or shall be the maximum labeled wattage of the luminaire.
- For line-voltage lighting track and plug-in busway, designed to allow the addition and/or relocation of luminaires without altering the wiring of the system, the wattage shall be
- the specified wattage of the luminaires included in the system with a minimum of 30 W/lin ft or
- the wattage limit of the system’s circuit breaker or
- the wattage limit of other permanent current-limiting device(s) on the system.
- The wattage of low-voltage lighting track, cable conductor, rail conductor, and other flexible lighting systems that allow the addition and/or relocation of luminaires without altering the
wiring of the system shall be the specified wattage of the transformer supplying the system.
- The wattage of all other miscellaneous lighting equipment shall be the specified wattage of the lighting equipment.
9.2 Compliance Path(s)
9.2.1 Lighting systems and equipment shall comply with Section 9.1. General; Section 9.4, Mandatory Provisions; and the prescriptive requirements
of either
- Section 9.5, Building Area Method; or
- Section 9.6, Space-by-Space Method.
9.2.2 Prescriptive Requirements
9.2.2.1 The Building Area Method for determining the interior lighting power allowance, described in Section 9.5, is a simplified
approach for demonstrating compliance.
9.2.2.2 The Space-by-Space Method, described in Section 9.6, is an alternative approach that allows greater flexibility.
9.2.2.3 Interior Lighting Power. The interior lighting power allowance for a building or a separately metered or permitted portion of a
building shall be determined by either the Building Area Method described in Section 9.5 or the Space-by-Space Method described in Section 9.6. Trade-offs of interior lighting power
allowance among portions of the building for which a different method of calculation has been used are not permitted. The installed interior lighting power identified in accordance with
Section 9.1.3 shall not exceed the interior lighting power allowance developed in accordance with Section 9.5 or 9.6.
Exception: The following lighting equipment and applications shall not be considered when determining the interior lighting power
allowance developed in accordance with Section 9.5 or 9.6, nor shall the wattage for such lighting be included in the installed interior lighting power identified in accordance with
Section 9.1.3. However, any such lighting shall not be exempt unless it is an addition to general lighting and is controlled by an independent control device.
- Display or accent lighting that is an essential element for the function performed in galleries, museums, and monuments.
- Lighting that is integral to equipment or instrumentation and is installed by its manufacturer.
- Lighting specifically designed for use only during medical or dental procedures and lighting integral to medical equipment.
- Lighting integral to both open and glass-enclosed refrigerator and freezer cases.
- Lighting integral to food warming and food preparation equipment.
- Lighting for plant growth or maintenance.
- Lighting in spaces specifically designed for use by occupants with special lighting needs including visual impairment and other medical and age-related issues.
- Lighting in retail display windows, provided the display area is enclosed by ceiling-height partitions.
- Lighting in interior spaces that have been specifically designated as a registered interior historic landmark.
- Lighting that is an integral part of advertising or directional signage.
- Exit signs.
- Lighting that is for sale or lighting educational demonstration systems.
- Lighting for theatrical purposes, including performance, stage, and film and video production.
- Lighting for television broadcasting in sporting activity areas.
- Casino gaming areas.
- Furniture-mounted supplemental task lighting that is controlled by automatic shutoff and complies with Section 9.4.1.4(d).
9.3 (Not Used)
9.4 Mandatory Provisions
9.4.1 Lighting Control
9.4.1.1 Automatic Lighting Shutoff. Interior lighting in buildings larger than 5000 ft2 shall be controlled with an
automatic control device to shut off building lighting in all spaces. This automatic control device shall function on either.
- a scheduled basis using a time-of-day operated control device that turns lighting off at specific programmed times—an independent program schedule shall be provided for areas of no more
than 25,000 ft2 but not more than one floor—or
- an occupant sensor that shall turn lighting off within 30 minutes of an occupant leaving a space or
- a signal from another control or alarm system that indicates the area is unoccupied.
Exceptions: The following shall not require an automatic control device:
- Lighting intended for 24-hour operation
- Lighting in spaces where patient care is rendered
- Lighting in spaces where an automatic shutoff would endanger the safety or security of the room or building occupant(s).
9.4.1.2 Space Control. Each space enclosed by ceiling height partitions shall have at least one control device to independently control the
general lighting within the space. Each manual device shall be readily accessible and located so the occupants can see the controlled lighting.
- A control device shall be installed that automatically turns lighting off within 30 minutes of all occupants leaving a space, except spaces with multi-scene control, in
- classrooms (not including shop classrooms, laboratory classrooms, and preschool through 12th grade classrooms),
- conference/meeting rooms, and
- employee lunch and break rooms.
These spaces are not required to be connected to other automatic lighting shutoff controls.
- For all other purposes, each control device shall be activated either manually by an occupant or automatically by sensing an occupant. Each control device shall control a maximum of 2500
ft2 area for a space 10,000 ft2 or less and a maximum of 10,000 ft2 area for a space greater than 10,000 ft2 and be capable of overriding any
time-of-day scheduled shutoff control for no more than four hours.
Exception: Remote location shall be permitted for reasons of safety or security when the remote control device has an indicator pilot light as
part of or next to the control device and the light is clearly labeled to identify the controlled lighting.
9.4.1.3 Exterior Lighting Control. Lighting for all exterior applications not exempted in Section 9.1 shall have automatic controls capable of
turning off exterior lighting when sufficient daylight is available or when the lighting is not required during nighttime hours. Lighting not designated for dusk-to-dawn operation shall be
controlled by either
- a combination of a photosensor and a time switch or
- an astronomical time switch
Lighting designated for dusk-to-dawn operation shall be controlled by an astronomical time switch or photosensor. All time switches shall be capable of retaining
programming and the time setting during loss of power for a period of at least ten hours.
Exception: Lighting for covered vehicle entrances or exits from buildings or parking structures where required for safety, security, or eye
adaptation.
9.4.1.4 Additional Control
- Display/Accent Lighting – display or accent lighting shall have a separate control device.
- Case Lighting – lighting in cases used for display purposes shall have a separate control device.
- Hotel and Motel Guest Room Lighting – hotel and motel guest rooms and guest suites shall have a master control device at the main room entry that controls all permanently
installed luminaires and switched receptacles.
- Task lighting – supplemental task lighting, including permanently installed under-shelf or under-cabinet lighting, shall have a control device integral to the luminaires or be
controlled by a wall-mounted control device provided the control device is readily accesible and located so that the occupant can see the controlled lighting.
- Non-visual lighting – lighting for non-visual applications, such as plant growth and food warming, shall have a separate control device.
- Demonstration lighting – lighting equipment that is for sale or for demonstrations in lighting education shall have a separate control device.
9.4.2 Tandem Wiring. Luminaires designed for use with one or three linear fluorescent lamps greater than 30W each shall use two-lamp tandem-wired
ballasts in place of single-lamp ballasts when two or more luminaires are in the same space and on the same control device.
Exceptions:
- Recessed luminaires more than 10 ft apart measured center to center.
- Surface-mounted or pendant luminaires that are not continuous.
- Luminaires using single-lamp high-frequency electronic ballasts.
- Luminaires using three-lamp high-frequency electronic or three-lamp electromagnetic ballasts.
- Luminaires on emergency circuits.
- Luminaires with no available pair.
9.4.3 Exit Signs. Internally illuminated exit signs shall not exceed 5W per face.
9.4.4 Exterior Building Grounds Lighting. All exterior building grounds luminaires that operate at greater than 100W shall contain lamps having a
minimum efficacy of 60 lm/W unless the luminaire is controlled by a motion sensor or qualifies for one of the exceptions under Section 9.1.1 or 9.4.5.
9.4.5 Exterior Building Lighting Power. The total exterior lighting power allowance for all exterior building applications is the sum of the
individual lighting power densities permitted in Table 9.4.5 for these applications plus an additional unrestricted allowance of 5% of that sum. Trade-offs are allowed only among exterior lighting
applications listed in the Table 9.4.5 “Tradable Surfaces” section.
Exceptions: Lighting used for the following exterior applications is exempt when equipped with a control device independent of the control of the
non-exempt lighting:
- Specialized signal, directional and marker lighting associated with transportation.
- Advertising signage or directional signage.
|
TABLE 9.4.5 Lighting Power Densities for Building Exteriors
|
|
Tradable Surfaces (LPDs for uncovered parking areas, building grounds, building entrances and exits, canopies and overhangs, and outdoor sales
areas may be traded.)
|
Uncovered parking areas |
Parking lots and drives |
0.15 W/ft2 |
| Building grounds |
Walkways less than 10 ft. wide |
1.0 W/linear foot |
|
Walkways 10 ft wide or greater
Plaza areas
Special feature areas |
0.2W/ft2 |
|
Stairways |
1.0W/ft2 |
| Building entrances and exits |
Main entries |
30 W/linear foot of door width |
|
Other doors |
20 W/linear foot of door width |
Canopies and overhangs
Canopies (free standing and attached and overhangs) |
1.25 W/ft2 |
Outdoor sales
Open areas (including vehicle sales lots) |
0.5 W/ft2 |
Street frontage for vehicle sales lots in addition to
“open area” allowance |
20W/linear foot |
|
Non-Tradable Surfaces (LPDs calculations for the following applications can be used only for the specific application and cannot be traded between
surfaces or with other exterior lighting. The following allowances are in addition to any allowance otherwise permitted in the “Tradable Surfaces” section of this table.)
|
Building facades |
0.2W/ft2 for each illuminated wall or
Surface or 5.0 W/linear foot for each
illuminated wall or surface length
|
| Automated teller machines and night depositories |
270 W per location plus 90 W per additional ATM per location
|
|
Entrances and gatehouse inspection stations at
guarded facilities
|
1.25 W/ft2 of uncovered area (covered areas are included in the “Canopies and Overhangs” section of “Tradable
Surfaces” |
Loading areas for law enforcement, fire, ambulance,
And other emergency service vehicles |
0.5 W/ft2of uncovered area (covered areas are included in the “Canopies and Overhangs” section of “Tradable
Surfaces” |
| Drive-through windows at fast food restaurants |
400 W per drive-through
|
| Parking near 24-hour retail entrances |
800 W per main entry |
- Lighting integral to equipment or instrumentation and installed by its manufacturer.
- Lighting for theatrical purposes, including performance, stage, film production, and video production.
- Lighting for athletic playing areas.
- Temporary lighting
- Lighting for industrial production, material handling, transportation sites, and associated storage areas.
- Theme elements in theme/amusement parks.
- Lighting used to highlight features of public monuments and registered historic landmark structures or buildings.
9.5 Building Area Method Compliance Path
9.5.1 Building Area Method of Calculating Interior Lighting Power Allowance. Use the following steps to determine the interior lighting power
allowance by the Building Area Method:
- Determine the appropriate building area type from Table 9.5.1 and the allowed LPD (watts per unit area) from the “Building Area Method” column. For building area type not listed,
selection of a reasonably equivalent type shall be permitted.
- Determine the gross lighted floor area (square feet) of the building area type.
- Multiply the gross lighted floor areas of the building area type(s) times the LPD.
- The interior lighting power allowance for the building is the sum of the lighting power allowances of all building area types. Trade-off among building area types are permitted provided that
the total installed interior lighting power does not exceed the interior lighting power allowance.
TABLE 9.5.1 Lighting Power Densities Using the Building Area Method
| Building Area Typea |
LPD (W/ft2) |
| Automotive Facility |
0.9 |
| Convention center |
1.2 |
| Courthouse |
1.2 |
| Dining: bar lounge/leisure |
1.3 |
| Dining: cafeteria/fast food |
1.4 |
| Dining: family |
1.6 |
| Dormitory |
1.0 |
| Exercise center |
1.0 |
| Gymnasium |
1.1 |
| Health-care clinic |
1.0 |
| Hospital |
1.2 |
| Hotel |
1.0 |
| Library |
1.3 |
| Manufacturing facility |
1.3 |
| Motel |
1.0 |
| Motion picture theater |
1.2 |
| Multifamily |
0.7 |
| Museum |
1.1 |
| Office |
1.0 |
| Parking garage |
0.3 |
| Penitentiary |
1.0 |
| Performing arts theater |
1.6 |
| Police/fire station |
1.0 |
| Post Office |
1.1 |
| Religious building |
1.3 |
| Retail |
1.5 |
| School/university |
1.2 |
| Sports arena |
1.1 |
| Town hall |
1.1 |
|
| Transportation |
1.0 |
| Warehouse |
0.8 |
| Workshop |
1.4 |
In cases where both a general building area type and a specific building area type are listed, the specific building area type shall apply.
9.6 Alternative Compliance Path: Space-by-Space Method
9.6.1 Space-by-Space Method of Calculating Interior Lighting power Allowance. Use the following steps to determine the interior lighting power
allowance by the Space-by-Space Method:
- Determine the appropriate building type from Table 9.61 For building types not listed, selection of a reasonably equivalent type shall be permitted.
- For each space enclosed by partitions 80% or greater than ceiling height, determine the gross interior floor area by measuring to the center of the partition wall. Including the floor area of
balconies or other projections. Retail spaces do not have to comply with the 80% partition height requirements.
- Determine the interior lighting power allowance by using the columns designated Space-by-Space Method in Table 9.6.1. Multiply the floor area(s) of the space(s) times the allowed LPD for the
space type that most closely represents the proposed use of the space(s). The products is the lighting power allowance for the space(s). The For space types not listed, selection of a reasonable
equivalent category shall be permitted.
- The interior lighting power allowance is the sum of lighting power allowances of all spaces. Trade-offs among spaces are permitted provided that the total installed interior lighting power
does not exceed the interior lighting power allowance.
9.6.2 Additional Interior Lighting Power. When using the Space-by-space Method, an increase in the interior lighting power allowance is allowed
for specific lighting functions. Additional power shall be allowed only if the specified lighting is installed and automatically controlled, separately from the general lighting, to be turned off
during non business hours. This additional power shall be used only for the specified luminaries and shall not be used for any other purpose.
An increase in the interior lighting power allowance is permitted in the following cases:
- For spaces in which lighting is specified to be installed in addition to the general lighting for the purpose of decorative appearance, such as chandelier-type luminaires or sconces or for
highlighting art or exhibits, provided that the additional lighting power shall not exceed 1.0 W/ft2 of such spaces.
- For lighting equipment installed in sales areas and specifically designed and directed to highlight merchandise, calculate the additional lighting power as follows
Additional Interior Lighting Power Allowance =
1000 watts + (Retail Area 1 x 1.0 W/ft2)
+ (Retail Area 2 x 1.7 W/ft2)
+ (Retail Area 3 x 2.6 W/ft2)
+ (Retail Area 4 x 4.2 W/ft2),
where
Retail Area 1 = the floor area for all products not listed in Retail Areas 2, 3 or 4;
Retail Area 2 = the floor area used for the sale of vehicles, sporting goods and small electronics;
Retail Area 3 = the floor area used for the sale of furniture, clothing, cosmetics and artwork; and
Retail Area 4 = the floor area used for the sale of jewelry, crystal and china.
Exception: Other merchandise categories may be included in Retail Areas 2 through 4 above, provided that justification documenting the need for additional lighting power based
on visual inspection, contrast, or other critical display is approved by the authority having jurisdiction.
9.7 Submittals (Not Used)
9.8 Product Information (Not Used)
LPD, W/ft2
TABLE 9.6.1 Lighting Power Densities Using the Space-by-Space Method
| Common Space Typesa |
LPD,W/ft2 |
| Office – Enclosed |
1.1 |
| Office – Open Plan |
1.1 |
| Conference/Meeting/Multipurpose |
1.3 |
| Classroom/Lecture/Training |
1.4 |
| For Pentientiary |
1.3 |
| Lobby |
1.3 |
| For Hotel |
1.1 |
| For Performing Arts Theater |
3.3 |
| For Motion Picture Theater |
1.1 |
| Audience/Seating Area |
0.9 |
| For Gymnasium |
0.4 |
| For Exercise Center |
0.3 |
| For Convention Center |
0.7 |
| For Penitentiary |
0.7 |
| For Religious Buildings |
1.7 |
| For Sports Arena |
0.4 |
| For Performing Arts Theater |
2.6 |
| For Motion Picture Theater |
1.2 |
| For Transportation |
0.5 |
| Atrium – First Three Floors |
0.6 |
| Atrium – Each Additional Floor |
0.2 |
| Lounge/Recreation |
1.2 |
| For Hospital |
0.8 |
| Dining Area |
0.9 |
| For Penitentiary |
1.3 |
| For Hotel |
1.3 |
| For Motel |
1.2 |
| For Bar Lounge/Leisure Dining |
1.4 |
| For Family Dining |
2.1 |
| Food Preparation |
1.2 |
| Laboratory |
1.4 |
| Restrooms |
0.9 |
| Dressing/Locker/Fitting Room |
0.6 |
| Corridor/Transition |
0.5 |
| For Hospital |
1.0 |
| For Manufacturing Facility |
0.5 |
| Stairs – Active |
0.6 |
| Active Storage |
0.8 |
| For Hospital |
0.9 |
| Inactive Storage |
0.3 |
| For Museum |
0.8 |
| Electrical/Mechanical |
1.5 |
| Building-Specific Space Types PD, |
LPD,W/ft2 |
| Gymnasium/Exercise Center |
|
| Playing Area |
1.4 |
| Exercise Area |
0.9 |
| Courthouse/Police Station/Penitentiary |
|
| Courtroom |
1.9 |
| Confinement Cells |
0.9 |
| Judges’ Chambers |
1.3 |
| Fire Stations |
|
| Engine Rooms |
0.8 |
| Sleeping Quarters |
0.3 |
| Post Office – Sorting Area |
|
| Convention Center – Exhibit Space |
1.3 |
| Library |
|
| Card File and Cataloging |
1.7 |
| Stacks |
1.2 |
| Reading Area |
1.2 |
| Hospital |
|
| Emergency |
2.7 |
| Recovery |
0.8 |
| Nurses’ Station |
1.0 |
| Exam/Treatment |
1.5 |
| Pharmacy |
1.2 |
| Patient Room |
0.7 |
| Operating Room |
2.2 |
| Nursery |
0.6 |
| Medical Supply |
1.4 |
| Physical Therapy |
0.9 |
| Radiology |
0.4 |
| Laundry – Washing |
0.6 |
| Automotive – Service/Repair |
0.7 |
| Manufacturing |
|
| Low Bay (<25 ft Floor to Ceiling Height) |
1.2 |
| High Bay (>25 ft Floor to Ceiling Height) |
1.2 |
| Detailed Manufacturing |
2.1 |
| Equipment Room |
1.2 |
| Control Room |
0.5 |
| Hotel/Motel Guest Rooms |
1.1 |
| Dormitory –Living Quarters |
1.1 |
| Museum |
|
| General Exhibition |
1.0 |
| Restoration |
1.7 |
| Bank/Office – Banking Activity Area |
1.5 |
TABLE 9.6.1 Lighting Power Densities Using the Space-by-Space Method (continued)
| Common Space Typesa |
LPD,W/ft2 |
| Workshop |
1.9 |
| Sales Area [for accent lighting, see |
1.7 |
| Section 9.6.2 (b)] |
|
| Building-Specific Space Types |
LPD, W/ft2 |
| Religious Buildings |
|
| Worship Pulpit, Choir |
2.4 |
| Fellowship Hall |
0.9 |
| Retail |
|
| Sales Area [for accent lighting, see |
1.7 |
| Section 9.6.2 (b)] |
|
| Mall Concourse |
1.7 |
| Sports Arena |
0.9 |
| Ring Sports Area |
2.7 |
| Court Sports Area |
2.3 |
| Indoor Playing Field Area |
1.4 |
| Warehouse |
|
| Fine Material Storage |
1.4 |
| Medium/Bulky Material Storage |
0.9 |
| Parking Garage – Garage Area |
0.2 |
| Transportation |
|
| Airport – Concourse |
0.6 |
| Air/Train/Bus – Baggage Area |
1.0 |
| Terminal – Ticket Counter |
1.5 |
| Sports Arena |
0.9 |
Florida Business Code (FBC)
SECTION 13-415
LIGHTING
13-415.0 Applicability
13-415.1.ABC.1.1 Automatic lighting shutoff
13-415.1.ABC.1.2 Space control
13-415.1.ABC.1.3 Additional controls
13-415.1.ABC.1.4 Exterior lighting control
13-415.1.A Prescriptive requirements specific to Method A
13-415.1.B Prescriptive requirements specific to Method B
13-415.1.C Prescriptive requirements specific to Method C
13-415.2.ABC.1.2 Luminaire wattage
13-415.2.ABC.1.3 Exterior building lighting power TABLE 13-415.2.ABC.1.3 Lighting Power Limits for Bldg Exteriors TABLE 13-415.2.B Lighting Power Densities space-by-space
13-415.2.B.2 Additional interior lighting power
(back to top) 13-415.0 Applicability.
Lighting systems and equipment shall comply with the requirements of 415.1.ABC and applicable requirements of Section 415.2. This section shall apply to the following:
- Interior spaces of buildings;
- Exterior building features, including facades, illuminated roofs, architectural features, entrances, exits, loading docks, and illuminated canopies; and
- Exterior building grounds lighting provided through the building’s electrical service.
Exceptions :
- Emergency lighting that is automatically off during normal building operation,
- Lighting within living units,
- Lighting that is specifically designated as required by a health or life safety statute, ordinance, or regulation,
- Decorative gas lighting systems.
13-415.1 Prescriptive requirements.
13-415.1.ABC Basic prescriptive requirements for Methods A, B and C.
13-415.1.ABC.1 Controls.
(back to top) 13-415.1.ABC.1.1 Automatic lighting
shutoff.
Interior lighting in buildings larger than 5,000 square feet (465 m 2 ) shall be controlled with an automatic control device to shut off building lighting in all spaces. This automatic control
device shall function on either:
- A scheduled basis using a time-of-day operated control device that turns lighting off at specific programmed times - an independent program schedule shall be provided for areas of no more
than 25,000 square feet (2323 m²) but not more than one floor,
- An occupant sensor that shall turn lighting off within 30 minutes of an occupant leaving a space,
- A signal from another control or alarm system that indicates the area is unoccupied.
Exception: Lighting intended for 24-hour operation shall not require an automatic control device.
(back to top) 13-415.1.ABC.1.2 Space control.
Each space enclosed by ceiling-height partitions shall have at least one control device to independently control the general lighting within the space. Each control device shall be activated
either manually by an occupant or automatically by sensing an occupant. Each control device shall:
- Control a maximum of 2,500 square feet (232 m²) area for a space 10,000 square feet (929 m²) or less and a maximum of 10,000 square feet (929 m 2 ) area for a space greater than
10,000 square feet (929 m²), and
- Be capable of overriding any time-of-day scheduled shutoff control for no more than four hours.
Each manual control device shall be readily accessible and located so the occupant can see the controlled lighting.
Exception: Remote location shall be permitted for reasons of safety or security when the remote control device has an indicator pilot light as part of or next to
the control device and it shall be clearly labeled to identify the controlled lighting.
(back to top) 13-415.1.ABC.1.3 Additional controls.
Controls are required in the following cases:
- Display or accent lighting. Display or accent lighting shall have a separate control.
- Case lighting. Lighting in cases used for display purposes shall have a separate control device.
- Hotel and motel guest room lighting. Hotel and motel guest rooms and guest suites shall have a master control device at the main room entry that controls all permanently installed
luminaires and switched receptacles.
- Task lighting. Supplemental task lighting, including permanently installed under-shelf or under-cabinet lighting, shall have a control device integral to the luminaires or be controlled by
a wall-mounted control device provided the control device is readily accessible and located so that the occupant can see the controlled lighting.
- Nonvisual lighting. Lighting for nonvisual applications, such as plant growth and food warming, shall have a separate control device.
- Demonstration lighting. Lighting equipment that is for sale or for demonstrations in lighting education shall have a separate control device.
(back to top) 13-415.1.ABC.1.4 Exterior lighting
control.
Lighting for all exterior applications not exempted under 415.0 and 415.2.ABC.1.3 shall be controlled by a photosensor or astronomical time switch that is capable of automatically turning off the
exterior lighting when sufficient daylight is available or the lighting is not required.
Exception: Lighting for covered vehicle entrances or exits from buildings or parking structures where required for safety, security, or eye adaptation.
13-415.1.ABC.2 Exterior building grounds lighting.
All exterior building grounds luminaires that operate at greater than 100 watts shall contain lamps having a minimum efficacy of 60 lm/W unless the luminaire is controlled by a motion sensor or
qualifies for one of the exceptions under Sections 415.0 and 415.2.ABC.1.3.
13-415.1.ABC.3 Tandem wiring.
Luminaires designed for use with one or three linear fluorescent lamps >30W each shall use two-lamp tandem-wired ballasts in place of single lamp ballasts when two or more luminaires are in the
same space and on the same control device.
Exceptions:
- Recessed luminaires more than 10 feet (3048 mm) apart measured center to center.
- Surface-mounted or pendant luminaires that are not continuous.
- Luminaires using single-lamp high-frequency electronic ballasts.
- Luminaires using three-lamp high-frequency electronic or three-lamp electromagnetic ballasts.
- Luminaires on emergency circuits.
- Luminaires with no available pair.
13-415.1.ABC.4 Exit signs.
Exit sign luminaries operating at greater than 20 watts shall have a minimum source efficacy of 35 lm/W.
13-415.1.AB.1 Calculations.
All calculations and determinations of parameters used in the demonstration of compliance with this code by Methods A or B shall be conducted according to Section 415.2.
(back to top) 13-415.1.A
Prescriptive requirements specific to Method A.
Lighting levels and types determined by the FLA/COM Method A performance calculation to demonstrate compliance with this code shall be the maximum performance levels installed for lighting.
(back to top) 13-415.1.B
Prescriptive requirements specific to Method B.
Lighting levels and types determined by the FLA/COM Method B performance calculation to demonstrate compliance with this code shall be the maximum performance levels installed for lighting (see
Section 415.2.B ).
(back to top) 13-415.1.C
Prescriptive requirements specific to Method C.
See Section 415.2.C .
13-415.2 Performance calculation procedures.
13-415.2.ABC.1 Performance calculation procedures, General.
The interior lighting power allowance for a building or a separately metered or permitted portion of a building shall be determined by either the building area method described in Section 415.2.C.1
or the space-by-space method described in Section 415.2.B.1 . Trade-offs of interior lighting power allowance among portions of the building for which a different method of calculation has been
used are not permitted. The installed interior lighting power identified in accordance with Section 415.2.ABC.1.1 shall not exceed the interior lighting power allowance developed in accordance with
Section 415.2.C.1 or 415.2.B.1
Exceptions: The following lighting equipment and applications shall not be considered when determining the interior lighting power allowance developed in
accordance with Sections 415.2.C.1 or 415.2.B.1 , nor shall the wattage for such lighting be included in the installed interior lighting power identified in accordance with Section 415.2.ABC.1.1.
However, any such lighting shall not be exempt unless it is an addition to general lighting and is controlled by an independent control device.
- Display or accent lighting that is an essential element for the function performed in galleries, museums, and monuments.
- Lighting that is integral to equipment or instrumentation and is installed by its manufacturer.
- Lighting specifically designed for use only during medical or dental procedures and lighting integral to medical equipment.
- Lighting integral to both open and glass enclosed refrigerator and freezer cases.
- Lighting integral to food warming and food preparation equipment.
- Lighting for plant growth or maintenance.
- Lighting in spaces specifically designed for use by the visually impaired.
- Lighting in retail display windows, provided the display area is enclosed by ceiling-height partitions.
- Lighting in interior spaces that have been specifically designated as a registered interior historic landmark.
- Lighting that is an integral part of advertising or directional signage.
- Exit signs.
- Lighting that is for sale or lighting educational demonstration systems.
- Lighting for theatrical purposes, including performance,stage, and film and video production.
- Lighting for television broadcasting in sporting activity areas.
- Casino gaming areas.
13-415.2.ABC.1.1 Installed interior lighting power.
The installed interior lighting power shall include all power used by the luminaires, including lamps, ballasts, current regulators, and control devices except as specifically exempted in Section
415.2.ABC.1.
Exception: If two or more independently operating lighting systems in a space are capable of being controlled to prevent simultaneous user operation, the installed interior lighting power
shall be based solely on the lighting system with the highest wattage.
(back to top) 13-415.2.ABC.1.2 Luminaire wattage.
Luminaire wattage incorporated into the installed interior lighting power shall be determined in accordance with the following criteria:
- The wattage of incandescent or tungsten-halogen luminaires with medium screw base sockets and not containing permanently installed ballasts shall be the maximum labeled wattage of the
luminaire.
- The wattage of luminaires with permanently installed or remote ballasts or transformers shall be the operating input wattage of the maximum lamp/auxiliary combination based on values from
the auxiliary manufacturers literature or recognized testing laboratories.
- The wattage of line-voltage lighting track and plug-in busway that allow the addition and/or relocation of luminaires without altering the wiring of the system shall be the specified
wattage of the luminaries included in the system with a minimum of 30 watts per linear foot.
- The wattage of low-voltage lighting track, cable conductor, rail conductor, and other flexible lighting systems that allow the addition and/or relocation of luminaires without altering the
wiring of the system shall be the specified wattage of the transformer supplying the system.
- The wattage of all other miscellaneous lighting equipment shall be the specified wattage of the lighting equipment.
(back to top) 13-415.2.ABC.1.3 Exterior building
lighting power.
The exterior building facade lighting power shall not exceed 0.25 watts per square feet of the illuminated area. The exterior lighting power allowance for all other exterior building applications
is the sum of the lighting power limits permitted and specified in Table 415.2.ABC.1.3 for these applications. Exterior lighting for all applications (except those included in the exceptions to
Sections 415.0 and 415.2.ABC.1.3 ) shall comply with the requirements of Section 415.1.ABC.2.
Exceptions: Lighting used for the following exterior applications is exempt when equipped with an independent control device:
(a) specialized signal, directional, and marker lighting associated with transportation;
(b) lighting used to highlight features of public monuments and registered historic landmark structures or buildings; and
(c) lighting that is integral to advertising signage.
(back to top) TABLE 13-415.2.ABC.1.3
LIGHTING POWER LIMITS FOR BUILDING EXTERIORS
| Applications |
Power Limits |
| Building entrance with canopy or free standing canopy |
3 W/ft² of canopied area |
| Building entrance without canopy |
33 W/lin. ft.of door width |
| Building exit |
20 W/lin ft. of door width |
13-415.2.A Performance calculation procedures specific to Method A.
Calculation procedures for Method A shall be those incorporated in the FLA/COM program for Method A compliance.
13-415.2.B Performance calculation procedures specific to Method B.
Calculation procedures for Method B shall be those incorporated in the FLA/COM program for Method B compliance.
(back to top) TABLE 13-415.2.B
LIGHTING POWER DENSITIES USING THE SPACE-BY-SPACE METHOD
| Space-by-Space Method Lighting Power Density (LPD) |
| Common Space Types¹ |
LPD
(W/ft²) |
Building Specific Space Types (cont'd) |
LPD
(W/ft²) |
| Office-enclosed |
1.1 |
Gymnasium/Exercise Center |
|
| Office-open plan |
1.1 |
Playing Area |
1.4 |
| Conference/Meeting/Multipurpose |
1.3 |
Exercise Area |
0.9 |
| Classroom/Lecture/Training |
1.4 |
Fire Stations |
|
| Lobby |
1.3 |
Fire Station Engine Room |
0.8 |
| For Hotel |
1.1 |
Sleeping Quarters |
0.3 |
| For Performing Arts Theater |
3.3 |
Post Office-Sorting Area |
1.2 |
| For Motion Picture Theater |
1.1 |
Convention Center – Exhibit Space |
1.3 |
| Audience/Seating Area |
0.9 |
Library |
|
| For Gymnasium |
0.4 |
Card File & Cataloging |
1.1 |
| For Exercise Center |
0.3 |
Stacks |
1.7 |
| For Convention Center |
0.7 |
Reading Area |
1.2 |
| For Religious Buildings |
1.7 |
Hospital |
|
| For Sports Arenas |
0.4 |
Emergency |
2.7 |
| For Performing Arts Theater |
2.6 |
Recovery |
0.8 |
| For Motion Picture Theater |
1.2 |
Nurse Station |
1.0 |
| For Transportation |
0.5 |
Exam/Treatment |
1.5 |
| Atrium-first three floors |
0.6 |
Pharmacy |
1.2 |
| Atrium-each additional floors |
0.2 |
Patient Room |
0.7 |
| Lounge/Recreation |
1.2 |
Operating Room |
2.2 |
| For Hospital |
0.8 |
Nursery |
0.6 |
| Dining Area |
0.9 |
Medical Supply |
1.4 |
| For Hotel/Motel |
1.3 |
Physical Therapy |
0.9 |
| For Bar Lounge/Leisure Dining |
1.4 |
Radiology |
0.4 |
| For Family Dining |
2.1 |
Laundry-Washing |
0.6 |
| Food Preparation |
1.2 |
Automotive – Service/Repair |
0.7 |
| Laboratory |
1.4 |
Museum |
|
| Restrooms |
0.9 |
General Exhibition |
1.0 |
| Dressing/Locker/Fitting Room |
0.6 |
Restoration |
1.7 |
| Corridor/Transition |
0.5 |
Bank/Office – Banking Activity Area |
1.5 |
| For Hospital |
1.0 |
Religious Buildings |
|
| For Manufacturing Facility |
0.5 |
Worship-pulpit, choir |
2.4 |
| Stairs-active |
0.6 |
Fellowship Hall |
0.9 |
| Active Storage |
0.8 |
Retail |
|
| For Hospitals |
0.9 |
Grocery Sales Area |
2.0 |
| Inactive Storage |
0.3 |
Jewelry & Art Sales Area |
4.0 |
| For Museum |
0.8 |
Other Merchandise Sales Area |
2.0 |
| Electrical/Mechanical |
1.5 |
Mall Concourse |
1.5 |
| Workshop¹ |
1.9 |
Sports Arena |
|
| |
|
Ring Sports Area |
2.7 |
| Building Specific Space Types |
Court Sports Area |
2.3 |
| Indoor Plying Field Area |
1.4 |
| Canopies |
|
Warehouse |
|
| Under 15 feel in height |
1.5 |
Fine Material Storage |
1.4 |
| 15 feet and over in height |
2.0 |
Medium/Bulky Material Storage |
0.9 |
| |
|
Parking Garage – Garage Area |
0.2 |
| Courthouse/Police Station |
|
Transportation |
|
| Courtroom |
1.9 |
Airport - Concourse |
0.6 |
| Judges Chambers |
1.3 |
Air/Train/Bus – Baggage Area |
1.0 |
| |
|
Terminal – Ticket Counter |
1.5 |
For SI: 1 foot = 304.8 mm
¹ In cases where both a common space type and building specific space type are listed, the building specific space type shall apply.
13-415.2.B.1 Space-by-space method of calculating interior lighting power allowance.
FLA/COM uses the following steps to determine the interior lighting power allowance by the space-by-space method.
- Determine the appropriate building type from Table 415.2.B . For building types not listed, selection of a reasonably equivalent type shall be permitted.
- For each space enclosed by partitions 80 percent or greater than ceiling height, determine the gross interior floor area by measuring to the center of the partition wall. Include the floor
area of balconies or other projections. Retail spaces do not have to comply with the 80-percent partition height requirements.
- Determine the interior lighting power allowance by using the columns designated space-by-space method in Table 415.2.B . Multiply the floor area(s) of the space(s) times the allowed
lighting power density for the space type that most closely represents the proposed use of the space(s). The product is the lighting power allowance for the space(s). For space types not
listed, selection of a reasonable equivalent category shall be permitted.
- The interior lighting power allowance is the sum of lighting power allowances of all spaces. Trade-offs among spaces are permitted provided that the total installed interior lighting power
does not exceed the interior lighting power allowance.
(back to top) 13-415.2.B.2 Additional interior
lighting power.
When using the space-by-space method, an increase in the interior lighting power allowance is allowed for specific lighting functions. Additional power shall be allowed only if the specified
lighting is installed, shall be used only for the specified luminaires, and shall not be used for any other purpose or in any other space. An increase in the interior lighting power allowance is
permitted in the following cases:
- For spaces in which lighting is specified to be installed in addition to the general lighting for the purpose of decorative appearance, such as chandelier-type luminaries or sconces or for
highlighting art or exhibits, provided that the additional lighting power shall not exceed 1.0 watts per square foot of such spaces.
- For spaces in which lighting is specified to be installed to meet the requirements of visual display terminals as the primary viewing task, provided that the additional lighting power shall
not exceed 0.35 watts per square foot of such spaces and that the specified luminaire meets requirements for use in such spaces. Maximum average luminance measured from the vertical in candelas
per square foot of not more than 80 cd/ft² at 65 degrees, 33 cd/ft² at 75 degrees, and 17 cd/ft² at 85 to 90 degrees.
- For lighting equipment installed in retail spaces that is specifically designed and directed to highlight merchandise, provided that the additional lighting power shall not exceed:
(1) 1.6 watts per square foot times the area of specific display or
(2) 3.9 watts per square foot times the area of specific display for valuable merchandise, such as jewelry, fine apparel and accessories, china and
silver, art, and similar items, where detailed display and examination of merchandise are important.
(back to top) 13-415.2.C Performance calculation procedures specific to Method C.
13-415.2.C.1 Building area method of calculating interior lighting power allowance.
Use the following steps to determine the interior lighting power allowance by the building area method:
- Determine the appropriate building area type from Table 415.2.C.1 and the allowed lighting power density (watts per unit area) from the building area method column. For building area types
not listed, selection of a reasonably equivalent type shall be permitted.
- Determine the gross lighted floor area (square feet) of the building area type.
- Multiply the gross lighted floor areas of the building area type(s) times the lighting power density.
- The interior lighting power allowance for the building is the sum of the lighting power allowances of all building area types. Trade-offs among building area types are permitted provided
that the total installed interior lighting power does not exceed the interior lighting power allowance.
(back to top) TABLE 13-415.2.C.1
LIGHTING POWER DENSITIES USING
THE BUILDING AREA METHOD
| Building Area Type 1 |
Lighting Power Density (W/ft²) |
| Automotive Facility |
0.9 |
| Convention Center |
1.2 |
| Court House |
1.2 |
| Dining: Bar Lounge/Leisure |
1.3 |
| Dining: Cafeteria/Fast Food |
1.4 |
| Dining: Family |
1.5 |
| Dormitory |
1.0 |
| Excercise Center |
1.8 |
| Gymnasium |
1.1 |
| Healthcare – Clinic |
1.0 |
| Hospital |
1.2 |
| Hotel |
1.0 |
| Library |
1.3 |
| Manufacturing Facility |
1.3 |
| Motel |
1.0 |
| Motion Picture Theatre |
1.2 |
| Multi-Family |
0.7 |
| Museum |
1.1 |
| Office |
1.0 |
| Parking Garage |
0.3 |
| Penitentiary |
1.0 |
| Performing Arts Theater |
1.6 |
| Police/Fire Station |
1.0 |
| Post Office |
1.1 |
| Religious Building |
1.3 |
| Retail |
1.5 |
| School/University |
1.1 |
| Sports Arena |
1.1 |
| Town Hall |
1.0 |
| Transportation |
1.0 |
| Warehouse |
0.8 |
| Workshop |
1.4 |
1. In cases where both general building area type and a specific building type are listed, the specific building area type shall apply
IECC 2000
Section 805 Lighting Systems
805.2.1 Interior lighting controls
805.2.1.1 Bi-level switching
805.2.1.2 Guest rooms
805.2.2 Exterior lighting controls
Table 805.5.2 Interior Lighting Power 806.4.7 Interior lighting
Addendum 2001 - Additions to IECC 2000 805.2.2. Additional controls
805.2.1.1 Bi Level Switching 805.2.2.2 Automatic lighting shutoff
805.1 General. This section covers lighting system controls, the connection of ballasts, the maximum lighting power for interior applications, and the minimum acceptable lighting
equipment for exterior applications.
805.2 Lighting controls. Lighting systems shall be provided with the controls as required in sections 805.2.1 and 805.2.2.
805.2.1 Interior lighting
controls. Each area enclosed by walls or floor-to-ceiling partitions shall have at least one manual control for the lighting serving that area. The required controls shall be located within the
area served by the controls or be a remote switch that identifies the lights served and indicates their status.
Exceptions:
- Areas designated as security or emergency areas that must be continuously lighted.
- Lighting in stairways or corridors that are elements if the means of egress.
805.2.1.1 Bi-level switching. Each area that is required to have a manual control shall also allow the occupant to reduce the connected lighting load in a reasonably uniform illumination
pattern by at least 50 percent.
Exceptions:
- Areas that have only 1 luminaire.
- Areas that are controlled by an occupant-sensing device.
- Corridors, storerooms, rest rooms, or public lobbies.
- Guest rooms.
805.2.1.2 Guest rooms. Guest rooms in hotels, motels, boarding houses or buildings shall have at least one master switch at the main entry door that controls all permanently wired lighting
fixtures and switched receptacles, except those in the bathroom(s). Suites shall have a control meeting these requirements at the entry to each room or at the primary entry to the suite.
805.2.2 Exterior lighting controls. Automatic switching or photocell controls shall be provided for all exterior lighting not intended for 24-hour operation. Automatic time switches shall have
a combination seven-day and seasonal daylight program schedule adjustment, and a minimum 4- hour power backup.
805.3 Tandem wiring. One- or three- lamp fluorescent fixtures that are pendant- or surface- mounted in continuous rows or recess mounted in an accessible ceiling
and within 10 feet (3048mm) of each other shall be tandem wired.
Exceptions:
- Where electronic high-frequency ballasts are used.
- Luminaires not on the same switch control or in the same area.
Table 805.5.2
INTERIOR LIGHTING POWER
| BUILDING OR AREA TYPE |
ENTIRE BUILDING
(W/ft²) |
TENANT AREA OR PORTION OF BUILDING
(W/ft²) |
| Auditorium |
NA |
1.6 |
| Bank/financial institutiona |
NA |
2.0 |
| Classroom/lecture hallb |
NA |
1.6 |
| Convention,conference or meeting areaa |
NA |
1.5 |
| Corridor,restroom, support area |
NA |
0.8 |
| Dininga |
NA |
1.4 |
| Exercise centera |
1.4 |
1.1 |
| Exhibition hall |
NA |
3.3 |
| Grocery storec |
1.9 |
2.1 |
| Gymnasium playing surface |
NA |
1.9 |
| Hotel functiona |
NA |
2.4 |
| Industrial work,<20-foot ceiling height |
NA |
2.1 |
Industrial work, 20-foot ceiling height
|
NA |
3.0 |
| Kitchen |
NA |
2.2 |
| Librarya |
1.5 |
1.8 |
| Lobby--hotela |
NA |
1.9 |
| Lobby--othera |
NA |
1.0 |
| Mall, arcade, or atrium |
NA |
1.4 |
| Medical and clinical careb,d |
1.6 |
1.6 |
| Museumb |
1.6 |
1.6 |
| Officeb |
1.3 |
1.5 |
| Religious worshipa |
2.2 |
3.2 |
| Resturanta |
1.7 |
1.7 |
| Retail sales, wholesale showroomc |
1.9 |
2.1 |
| School |
1.5 |
NA |
| Storage, industrial and commercial |
0.6 |
1.0 |
| Theaters—motion pictures |
1.1 |
1.0 |
| Theaters—performance (a) |
1.4 |
1.5 |
| Other |
0.6 |
1.0 |
For SI: 1 foot= 304.8 mm, 1 Watts per square foot =W/0.0929 m².
NA = Not Applicable.
- Where lighting equipment is specified to be installed for decorative in addition to lighting equipment specified for general lighting and is switch or dimmed on circuits different from the
circuits for general lighting, the smaller of the actual wattage of the decorative lighting equipment or 1.0W/ft² times the are of the space that the decorative lighting equipment is in
shall be added to the interior lighting power determined in accordance with this line item.
- Where lighting equipment is specified to be installed to meet requirements of visual display terminals as the primary viewing task, the smaller of the actual wattage of the lighting equipment
or 0.35 W/ft² times the area of the space that the lighting equipment is in shall be added to the interior lighting power determined in accordance with this line item.
- Where lighting equipment is specified to be installed to highlight specific merchandise in addition to lighting equipment specified for general lighting and is switched or dimmed on circuits
different from the circuits for general lighting the smaller of the actual wattage of the lighting equipment installed specifically for merchandise, or 1.6 W/ft² times the area of the
specific display, or 3.9 W/ft² times the actual case or shelf area for displaying and selling fine merchandise such as jewelry, fine apparel and accessories, or china and silver, shall be
added to the interior lighting power determined in accordance with this line item.
- Where lighting equipment is specified to be installed, the smaller of the actual wattage of the lighting equipment, or 1.0 W/ft² times the area of the emergency, recovery, medical supply
and pharmacy space shall be added to the interior lighting power determined in accordance with this line item.
…
806.4.7 Interior lighting. The lignting power for the standaed design shall be the maximum allowed in accodance with Section 805.4. Where the occupancy of the building is not known, the
lighting power density shall be 1.5 warrs per square foot (16.1 W/m2)
Addendum 2001 - Additions to IECC 2000
Section 805.2. Change to read as follows:
(EC47-00)
805.2 Lighting controls. Lighting systems shall be provided with controls as required in Section 805.2.1, 805.2.2 and 805.2.3.
Section 805.2.2. Add new section to read as follows and renumber remaining sections:
(EC47-00)
805.2.2. Additional controls. Each area that is required to have a manual control shall have additional controls that meet the requirements of Sections 805.2.2.1, 805.2.2.2 or 805.2.2.3.
Exceptions:
- Areas that have only 1 luminaire.
- Areas that are controlled by an occupant-sensing device.
- Corridors, storerooms, restrooms, or public lobbies.
Secction 805.2.1.1. Change to read as follows:
(EC47-00)
805.2.1.1 Bi Level Switching. Each area less than 250 ft² (23m²) that is required to have a manual control shall also allow the occupant to reduce the connected lighting load in a
reasonably uniform illumination pattern by at least 50 percent.
Exceptions:
- Areas that have only 1 luminaire.
- Areas that are controlled by an occupant-sensing device.
- Corridors, storerooms, restrooms, or public lobbies.
- Guest rooms.
Section 805.2.2.2. Add new section as follows:
(EC47-00)
805.2.2.2 Automatic lighting shutoff. Spaces greater than 250² (23m²) in buildings larger than 5,000ft² (465m²) shall be equipped with an automatic control device to shut
off lighting in those spaces. This automatic control device shall function on either:
- A scheduled basis, using time-of-day, with an independent program schedule that controls the interior lighting in areas that do not exceed 25,000 ft² (2323 m²) and are not more than
one floor, or
- An unscheduled basis by occupant intervention.
IECC 2001
Section 805.2. Change to read as follows:
(EC47-00)
805.2 Lighting controls. Lighting systems shall be provided with controls as required in Section 805.2.1, 805.2.2 and 805.2.3.
Section 805.2.2. Add new section to read as follows and renumber remaining sections:
(EC47-00)
805.2.2. Additional controls. Each area that is required to have a manual control shall have additional controls that meet the requirements of Sections 805.2.2.1,
805.2.2.2 or 805.2.2.3.
Exceptions:
- Areas that have only 1 luminaire.
- Areas that are controlled by an occupant-sensing device.
- Corridors, storerooms, restrooms, or public lobbies.
Secction 805.2.1.1. Change to read as follows:
(EC47-00)
805.2.1.1 Bi Level Switching. Each area less than 250 ft² (23m²) that is required to have a manual control shall also allow the occupant to reduce the
connected lighting load in a reasonably uniform illumination pattern by at least 50 percent.
Exceptions:
- Areas that have only 1 luminaire.
- Areas that are controlled by an occupant-sensing device.
- Corridors, storerooms, restrooms, or public lobbies.
- Guest rooms.
Section 805.2.2.2. Add new section as follows:
(EC47-00)
805.2.2.2 Automatic lighting shutoff. Spaces greater than 250² (23m²) in buildings larger than 5,000ft² (465m²) shall be equipped with an
automatic control device to shut off lighting in those spaces. This automatic control device shall function on either:
- A scheduled basis, using time-of-day, with an independent program schedule that controls the interior lighting in areas that do not exceed 25,000 ft² (2323 m²) and are not more than
one floor, or
- An unscheduled basis by occupant intervention.
IECC 2003
SECTION 805
ELECTRICAL POWER AND LIGHTING SYSTEMS
805.2.1 Interior lighting controls
805.2.2 Additional controls
805.2.2.1 Light reduction controls
805.2.2.2 Automatic lighting shutoff
805.2.2.2.1 Occupant override
805.2.2.2.2 Holiday scheduling
805.2.2.3 Guestrooms
805.2.3 Exterior lighting controls
805.5 Interior lighting power requirements
805.5.1.4 Line-voltage lighting track
805.6 Exterior lighting Table 805.5.2 Interior Lighting Power
805.1 General. This section covers lighting system controls, the connection of ballasts, the maximum lighting power for interior applications, and minimum acceptable lighting equipment
for exterior applications.
Exception: Lighting within dwelling units.
805.2 Lighting controls. Lighting systems shall be provided with controls as required in Sections 805.2.1, 805.2.2 and 805.2.3.
805.2.1 Interior lighting controls. Each area enclosed by walls or floor-to-ceiling partitions shall have at least one manual control for the lighting serving that area. The required
controls shall be located within the area served by the controls or be a remote switch that identifies the lights served and indicates their status.
Exceptions:
- Areas designated as security or emergency areas that must be continuously lighted.
- Lighting in stairways or corridors that are elements of the means of egress.
805.2.2 Additional controls. Each area that is required to have a manual control shall have additional controls that meet the requirements of Sections 805.2.2.1, 805.2.2.2 and 805.2.2.3.
Exceptions:
- Areas that have only one luminaire.
- Areas that are controlled by an occupant-sensing device.
- Corridors, storerooms, restrooms or public lobbies.
805.2.2.1 Light reduction controls. Each area that is required to have a manual control shall also allow the occupant to reduce the connected lighting load in a reasonably uniform
illumination pattern by at least 50 percent. Lighting reduction shall be achieved by one of the following or other approved method:
- Controlling all lamps or luminaries;
- Dual switching of alternate rows of luminaires, alternate luminaires or alternate lamps;
- Switching the middle lamp luminaires independently of the outer lamps; or
- Switching each luminaire or each lamp.
Exceptions:
- Areas that have only one luminaire.
- Areas that are controlled by an occupant-sensing device.
- Corridors, storerooms, restrooms or public lobbies.
- Guestrooms.
- Spaces that use less than 0.6 Watts per square foot (6.5 W/m).
805.2.2.2 Automatic lighting shutoff. Buildings larger than 5,000 square feet (465m²) shall be equipped with an automatic control device to shut off lighting in those areas. This
automatic control device shall function on either:
- A scheduled basis, using time-of-day, with an independent program schedule that controls the interior lighting in areas that do not exceed 25,000 square feet (2323 m²) and are not more
than one floor; or
- An unscheduled basis by occupant intervention.
805.2.2.2.1 Occupant override. Where an automatic time switch control device is installed to comply with Section 805.2.2.2, Item 1, it shall incorporate an override switching device
that:
- Is readily accessible.
- Is located so that a person using the device can see the lights or the area controlled by that switch, or so that the area being lit is annunciated.
- Is manually operated.
- Allows the lighting to remain on for no more than 2 hours when an override is initiated.
- Controls an area not exceeding 5,000 square feet (465 m²).
Exceptions:
- 1. In malls and arcades, auditoriums, single- tenant retail spaces, industrial facilities and arenas, where captive-key override is utilized, override time may exceed 2 hours.
- 2. In malls and arcades, auditoriums, single- tenant retail spaces, industrial facilities and arenas, the area controlled may not exceed 20,000 square feet (1860 m²).
805.2.2.2.2 Holiday scheduling. If an automatic time switch control device is installed in accordance with Section 805.2.2.2, Item 1, it shall incorporate an automatic holiday scheduling
feature that turns off all loads for at least 24 hours, then resumes the normally scheduled operation.
Exception: Retail stores and associated malls, restaurants, grocery stores, churches and theaters.
805.2.2.3 Guestrooms. Guestrooms in hotels, motels, boarding houses or similar buildings shall have at least one master switch at the main entry door that controls all permanently wired
lighting fixtures and switched receptacles, except those in the bathroom(s). Suites shall have a control meeting these requirements at the entry to each room or at the primary entry to the
suite.
805.2.3 Exterior lighting controls. Automatic switching or photocell controls shall be provided for all exterior lighting not intended for 24-hour operation. Automatic time switches shall
have a combination seven-day and seasonal daylight program schedule adjustment, and a minimum 4-hour power backup.
805.3 Tandem wiring. The following luminaires located within the same area shall be tandem wired:
- Fluorescent luminaires equipped with one, three or odd numbered lamp configurations, that are recess-mounted within 10 feet (3048mm)center-to-center of each other.
- Fluorescent luminaires equipped with one, three or any other odd-numbered lamp configuration, that are pendant- or surface-mounted within 1 foot (305 mm) edge-to-edge of each other.
Exceptions:
- Where electronic high-frequency ballasts are used.
- Luminaires on emergency circuits.
- Luminaires with no available pair in the same area.
805.4 Exit signs. Internally illuminated exit signs shall not exceed 5 Watts per side.
805.5 Interior lighting power requirements. A building complies with this section if its total connected lighting power calculated under Section 805.5.1 is no greater than the interior
lighting power calculated under Section 805.5.2.
805.5.1 Total connected interior lighting power. The total connected interior lighting power(Watts) shall be the sum of the watts of all interior lighting
equipment as determined in accordance with Sections 805.5.1.1 through 805.5.1.4.
Exceptions: The connected power associated with the following lighting equipment is not included in calculating total connected lighting power.
- Specialized medical, dental and research lighting.
- Professional sports arena playing field lighting.
- Display lighting for exhibits in galleries, museums and monuments.
- Guestroom lighting in hotels, motels, boarding houses or similar buildings.
- Emergency lighting automatically off during normal building operation.
805.5.1.1 Screw lamp holders. The wattage shall be the maximum labeled wattage of the luminaire.
805.5.1.2 Low-voltage lighting. The wattage shall be the specified wattage of the transformer supplying the system.
805.5.1.3 Other luminaires. The wattage of all other lighting equipment shall be the wattage of the lighting equipment verified through data furnished by the
manufacturer or other approved sources.
805.5.1.4 Line-voltage lighting track and plug-in bus way. The wattage shall be the greater of the wattage of the luminaires determined in accordance with Sections 805.5.1.1 through
805.5.1.3 or 30 W/linear foot (98W/lin m).
805.5.2 Interior lighting power. The interior lighting power shall be calculated using Section 805.5.2.1 or 805.5.2.2 as applicable.
805.5.2.1 Entire building method. Under this approach, the interior lighting power (Watts) is the value from Table 805.5.2 for the building type times the
conditioned floor area of the entire building. The interior lighting power (Watts) shall not be increased by the allowances contained in the footnotes of Table 805.5.2 when using the entire
building method.
805.5.2.2 Tenant area or portion of building method. The total interior lighting power (Watts) is the sum of all interior lighting powers for all areas in the
building covered in this permit. The interior lighting power is the conditioned floor area for each area type listed in Table 805.5.2 times the value from Table 805.5.2 for that area. For the
purposes of this method, an "area" shall be defined as all contiguous spaces that accommodate or are associated with a single area type as listed in Table 805.5.2. When this method is used to
calculate the total interior lighting power for an entire building, each area type shall be treated as a separate area.
805.6 Exterior lighting. When the power for exterior lighting is supplied through the energy service to the building, all exterior lighting, other than low-voltage landscape lighting, shall
have a source efficacy of at least 45 lumens per Watt.
Exception: Where approved because of historical, safety, signage or emergency considerations.
805.7 Electrical energy consumption. In buildings having individual dwelling units, provisions shall be made to determine the electrical energy consumed by each tenant by separately
metering individual dwelling units.
Table 805.5.2
INTERIOR LIGHTING POWER
| BUILDING OR AREA TYPE |
ENTIRE BUILDING
(W/ft²) |
TENANT AREA OR PORTION OF BUILDING
(W/ft²) |
| Auditorium |
Not Applicable |
1.8 |
| Automotive facility |
0.9 |
Not Applicable |
| Bank/financial institution (a) |
Not Applicable |
1.5 |
| Classroom/lecture hall (b) |
Not Applicable |
1.4 |
| Convention,conference or meeting center (a) |
1.2 |
1.3 |
| Cooridor,restroom, support area |
Not Applicable |
0.9 |
| Courthouse/town hall |
1.2 |
Not Applicable |
| Dining(a) |
Not Applicable |
0.9 |
| Dormitory |
1.0 |
NA |
| Exercise center (a) |
1.0 |
0.9 |
| Exhibition hall |
Not Applicable |
1.3 |
| Grocery store (c) |
1.5 |
1.6 |
| Gymnasium playing surface |
Not Applicable |
1.4 |
| Hotel function (a) |
1.0 |
1.3 |
| Industrial work,<20-foot ceiling height |
Not Applicable |
1.2 |
Industrial work,>20-foot ceiling height
|
Not Applicable |
1.7 |
| Kitchen |
Not Applicable |
1.2 |
| Library (a) |
1.3 |
1.7 |
| Lobby--hotel (a) |
Not Applicable |
1.1 |
| Lobby--other (a) |
Not Applicable |
1.3 |
| Mall, arcade, or atrium |
Not Applicable |
0.6 |
| Medical and clinical care (b,d) |
1.2 |
1.2 |
| Motel |
1.0 |
Not Applicable |
| Multifamily |
0.7 |
Not Applicable |
| Museum (b) |
1.1 |
1.0 |
| Office (b) |
1.0 |
1.1 |
| Parking Garage |
0.3 |
Not Applicable |
| Penitentiary |
1.0 |
Not Applicable |
| Police/fire station |
1.0 |
Not Applicable |
| Post Office |
1.1 |
Not Applicable |
| Religious worship (a) |
1.3 |
2.4 |
| Resturant (a) |
1.6 |
0.9 |
| Retail sales, wholesale showroom (c) |
1.5 |
1.7 |
| School |
1.2 |
Not Applicable |
| Storage, industrial and commercial |
0.8 |
0.8 |
| Theaters--motion pictures |
1.2 |
1.2 |
| Theaters--performance (a) |
1.6 |
2.6 |
| Transportation |
1.0 |
Not Applicable |
| Other |
0.6 |
1.0 |
For SI: 1foot =304.8mm, 1 Watts per square foot = W/0.0929 m²
(a) Where lighting equipment is specified to be installed for decorative appearances in addition to lighting equipment specified for general lighting and is switched or dimmed on circuits
different from the circuits for general lighting, the smaller of the actual wattage of the decorative lighting equipment or 1.0W/ft² times the area of the space that the decorative
lighting equipment is in shall be added to the interior lighting power determined in accordance with this line item.
(b) Where lighting equipment is specified to be installed to meet requirements of visual display terminals as the primary viewing task, the smaller of the actual wattage of the lighting
equipment or 0.35W/ft² times the area of the space that the lighting equipment is in shall be added to the interior lighting power determined in accordance with this line item.
(c) Where lighting equipment is specified to be installed to highlight specific merchandise in addition to lighting equipment specified for general lighting and is switched or dimmed on the
circuits different from the circuits for general lighting, the smaller of the actual wattage of the lighting equipment installed specifically for merchandise or, 1.6W/ft² times the
area of the specific display or , 39 W/ft² times the actual case or shelf area for displaying and selling fine merchandise such as jewelry, fine apparel and accessories, or china and
silver, shall be added to the interior lighting power determined in accordance with this line item.
(d) Where lighting equipment is specified to be installed, the smaller of the actual wattage of the lighting equipment, or 1.0W/ft² times the area of the emergency, recovery, medical
supply and pharmacy space shall be added to the interior lighting power determined in accordance with this line item.
|
806.4.7 Interior lighting. The lighting power for the standard design shall be the maximum allowed in accordance with Section 805.4. Where the occupancy of the
building is not known, the lighting power density shall be 1.5 Watts per square foot (16.1 W/ft² ).
IECC 2006
SECTION 505
ELECTRICAL POWER AND LIGHTING SYSTEMS
(Mandatory)
505.1 General. (Mandatory). This section covers lighting system controls, the connection of ballasts, the maximumlighting power for interior applications, and minimum acceptable lighting
equipment for exterior applications.
Exception: Lighting within dwelling units.
505.2 Lighting controls. (Mandatory). Lighting systems shall be provided with controls as required in Sections 505.2.1, 505.2.2 , 505.2.3 and 505.2.4.
505.2.1 Interior lighting controls. Each area enclosed by walls or floor-to-ceiling partitions shall have at least one manual control for the lighting serving that area. The required
controls shall be located within the area served by the controls or be a remote switch that identifies the lights served and indicates their status.
Exceptions:
- Areas designated as security or emergency areas that must be continuously lighted.
- Lighting in stairways or corridors that are elements of the means of egress.
505.2.2 Additional controls. Each area that is required to have a manual control shall have additional controls that meet the requirements of Sections 505.2.2.1 and 505.2.2.2.
505.2.2.1 Light reduction controls. Each area that is required to have a manual control shall also allow the occupant to reduce the connected lighting load in a reasonably uniform
illumination pattern by at least 50 percent. Lighting reduction shall be achieved by one of the following or other approved method:
- Controlling all lamps or luminaires;
- Dual switching of alternate rows of luminaires, alternate luminaires or alternate lamps;
- Switching the middle lamp luminaires independently of the outer lamps; or
- Switching each luminaire or each lamp.
Exceptions:
- Areas that have only one luminaire.
- Areas that are controlled by an occupant-sensing device.
- Corridors, storerooms, restrooms or public lobbies.
- Sleeping unit (see Section 505.2.3).
- Spaces that use less than 0.6 watts per square foot (6.5 W/m2).
505.2.2.2 Automatic lighting shutoff. Buildings larger than 5,000 square feet (465m2) shall be equipped with an automatic control device to shut off lighting in those areas. This
automatic control device shall function on either:
- A scheduled basis, using time-of-day, with an independent program schedule that controls the interior lighting in areas that do not exceed 25,000 square feet (2323 m2) and are not more than
one floor; or
- An occupant sensor that shall turn lighting off within 30 minutes of an occupant leaving a space; or
- A signal from another control or alarm system that indicates the area is unoccupied.
Exception: The following shall not require an automatic control device:
- Sleeping unit (see Section 505.2.3).
- Lighting in spaces where patient care is directly provided.
- Spaces where an automatic shutoff would endanger occupant safety or security.
505.2.2.2.1 Occupant override. Where an automatic time switch control device is installed to comply with Section 505.2.2.2, Item 1, it shall incorporate an override switching device that:
- Is readily accessible.
- Is located so that a person using the device can see the lights or the area controlled by that switch, or so that the area being lit is annunciated.
- Is manually operated.
- Allows the lighting to remain on for no more than 2 hours when an override is initiated.
- Controls an area not exceeding 5,000 square feet (465 m2).
Exceptions:
- In malls and arcades, auditoriums, single- tenant retail spaces, industrial facilities and arenas, where captive-key override is utilized, override time may exceed 2 hours.
- In malls and arcades, auditoriums, single- tenant retail spaces, industrial facilities and arenas, the area controlled may not exceed 20,000 square feet (1860 m2).
505.2.2.2.2 Holiday scheduling. If an automatic time switch control device is installed in accordance with Section 505.2.2.2, Item 1, it shall incorporate an automatic holiday
scheduling feature that turns off all loads for at least 24 hours, then resumes the normally scheduled operation.
Exception: Retail stores and associated malls, restaurants, grocery stores, places of religious worship and theaters.
505.2.3 Sleeping unit. Sleeping units in hotels, motels, boarding houses or similar buildings shall have at least one master switch at the main entry door that controls all permanently
wired luminaires and switched receptacles, except those in the bathroom(s). Suites shall have a control meeting these requirements at the entry to each room or at the primary entry to the
suite.
505.2.4 Exterior lighting controls. Lighting for all exterior applications shall have automatic controls capable of turning off exterior lighting when sufficient daylight is available
or when the lighting is not required during nighttime hours. Lighting not designated for dusk-to-dawn operation shall be controlled by an astronomical time switch. Lighting designated for
dusk-to-dawn operation shall be controlled by an astronomical time switch or photosensor. Astronomical time switches shall be capable of retaining programming and the time setting during loss of
power for a period of at least 10 hours.
Exception: Lighting for covered vehicle entrances or exits from buildings or parking structures where required for safety, security, or eye adaptation.
505.3 Tandem wiring. (Mandatory). The following luminaires located within the same area shall be tandem wired:
- Fluorescent luminaires equipped with one, three or odd-numbered lamp configurations, that are recess-mounted within 10 feet (3048 mm) center-to-center of each other.
- Fluorescent luminaires equipped with one, three or any other odd-numbered lamp configuration, that are pendant- or surface-mounted within 1 foot (305 mm) edge-to-edge of each other.
Exceptions:
- Where electronic high-frequency ballasts are used.
- Luminaires on emergency circuits.
- Luminaires with no available pair in the same area.
505.4 Exit signs. (Mandatory). Internally illuminated exit signs shall not exceed 5 Watts per side.
505.5 Interior lighting power requirements. (Prescriptive). A building complies with this section if its total connected lighting power calculated under Section 505.5.1 is no greater than
the interior lighting power calculated under Section 505.5.2.
505.5.1 Total connected interior lighting power. The total connected interior lighting power (watts) shall be the sum of the watts of all interior lighting equipment as determined in
accordance with Sections 505.5.1.1 through 505.5.1.4.
Exceptions: The connected power associated with the following lighting equipment is not included in calculating total connected lighting power.
- Specialized medical, dental and research lighting.
- Professional sports arena playing field lighting.
- Display lighting for exhibits in galleries, museums and monuments.
- Sleeping unit lighting in hotels, motels, boarding houses or similar buildings.
- Emergency lighting automatically off during normal building operation.
505.5.1.1 Screw lamp holders. The wattage shall be the maximum labeled wattage of the luminaire.
505.5.1.2 Low-voltage lighting. The wattage shall be the specified wattage of the transformer supplying the system.
505.5.1.3 Other luminaires. The wattage of all other lighting equipment shall be the wattage of the lighting equipment verified through data furnished by the manufacturer or other
approved sources.
505.5.1.4 Line-voltage lighting track and plug-in busway. The wattage shall be the greater of the wattage of the luminaires determined in accordance with Sections 505.5.1.1 through
505.5.1.3 or 30 W/linear foot (98W/lin m).
505.5.2 Interior lighting power. The total interior lighting power (watts) is the sum of all interior lighting powers for all areas in the building covered in this permit. The interior
lighting power is the floor area for each building area type listed in Table 505.5.2 times the value from Table 505.5.2 for that area. For the purposes of this method, an “area” shall
be defined as all contiguous spaces that accommodate or are associated with a single building area type as listed in Table 505.5.2. When this method is used to calculate the total interior
lighting power for an entire building, each building area type shall be treated as a separate area.
505.6 Exterior lighting. (Mandatory). When the power for exterior lighting is supplied through the energy service to the building, all exterior lighting, other than low-voltage landscape
lighting, shall comply with Sections 505.6.1 and 505.6.2.
Exception: Where approved because of historical, safety, signage or emergency considerations.
505.6.1 Exterior building grounds lighting. All exterior building grounds luminaires that operate at greater than 100 watts shall contain lamps having a minimum efficacy of 60 lumens
per watt unless the luminaire is controlled by a motion sensor or qualifies for one of the exceptions under Section 505.6.2.
TABLE 505.5.2
INTERIOR LIGHTING POWER ALLOWANCES
|
LIGHTING POWER DENSITY
|
|
Building Area Typea
|
(W/ft2)
|
|
Automotive Facility
|
0.9
|
|
Convention Center
|
1.2
|
|
Court House
|
1.2
|
|
Dining: Bar Lounge/Leisure
|
1.3
|
|
Dining: Cafeteria/Fast Food
|
1.4
|
|
Dining: Family
|
1.6
|
|
Dormitory
|
1.0
|
|
Exercise Center
|
1.0
|
|
Gymnasium
|
1.1
|
|
Healthcare-Clinic
|
1.0
|
|
Hospital
|
1.2
|
|
Hotel
|
1.0
|
|
Library
|
1.3
|
|
Manufacturing Facility
|
1.3
|
|
Motel
|
1.0
|
|
Motion Picture Theater
|
1.2
|
|
Multi-Family
|
0.7
|
|
Museum
|
1.1
|
|
Office
|
1.0
|
|
Parking Garage
|
0.3
|
|
Penitentiary
|
1.0
|
|
Performing Arts Theater
|
1.6
|
|
Police/Fire Station
|
1.0
|
|
Post Office
|
1.1
|
|
Religious Building
|
1.3
|
|
Retailb
|
1.5
|
|
School/University
|
1.2
|
|
Sports Arena
|
1.1
|
|
Town Hall
|
1.1
|
|
Transportation
|
1.0
|
|
Warehouse
|
0.8
|
|
Workshop
|
1.4
|
For SI: 1 foot = 304.8 mm, 1 watt per square foot = W/0.0929 m 2.
- In cases where both a general building area type and a more specific building area type are listed, the more specific building area type shall apply.
- Where lighting equipment is specified to be installed to highlight specific merchandise in addition to lighting equipment specified for general lighting and is switched or dimmed on
circuits different from the circuits for general lighting, the smaller of the actual wattage of the lighting equipment installed specifically for merchandise, or 1.6 W/ft2 times the
area of the specific display but not to exceed 50% of the floor area, or 3.9 W/ft2 times the actual case or shelf area for displaying and selling jewelry, china or silver, shall be
added to the interior lighting power determined in accordance with this line item.
505.6.2 Exterior building lighting power. The total exterior lighting power allowance for all exterior building applications is the sum of the individual lighting power allowances based
on the densities permitted in Table 505.6.2 for these applications plus an additional unrestricted allowance of 5 percent of that sum. Tradeoffs are allowed only among exterior lighting
applications listed in Table 505.6.2 in the Tradable Surfaces section. Exterior lighting for all applications (except those included in the exceptions to Section 505.6.2) shall comply with the
requirements of Section 505.6.1.
Exceptions: Lighting used for the following exterior applications is exempt when equipped with a control device independent of the control of the nonexempt lighting:
- Specialized signal, directional, and marker lighting associated with transportation;
- Advertising signage or directional signage;
- Integral to equipment or instrumentation and is installed by its manufacturer;
- Theatrical purposes, including performance, stage, film production and video production;
- Athletic playing areas;
- Temporary lighting;
- Industrial production, material handling, transportation sites, and associated storage areas;
- Theme elements in theme/amusement parks; and
- Used to highlight features of public monuments and registered historic landmark structures or buildings.
TABLE 505.6.2
LIGHTING POWER DENSITIES FOR BUILDING EXTERIORS
|